Rockwell Automation 23P PowerFlex DC Stand Alone Regulator and Gate Amplifier User Manual
Page 49
![background image](/manuals/576844/49/background.png)
Rockwell Automation Publication 23P-UM001D-EN-P - July 2012
49
Gate Amplifier Installation and Wiring
Chapter 3
Table 11 - Indicators and Control Connection Descriptions
GPS
The +28V Gate power supply provides all of the DC power for the Gate
Amplifier. All other voltages are derived from the +28V Gate power supply. If the
GPS LED is off, all of the other indicating LEDs will also be off. Confirm that
120VAC is present at the power input terminal if the GPS LED is not
illuminated.
LPS
The +5V Logic Power Supply voltage is derived from the +28V Gate power
supply. If the +28V Gate power supply power is not present the logic power
supply LED will not be illuminated.
No. Label on Gate Amplifier
Description
Function
GPS
+28V Gate Power Supply output present LED
This LED is illuminated when the gate power supply output is
present. See
below for more information.
LPS
+5V Logic Power Supply output present LED
This LED is illuminated when the logic power supply output is
present. See
below for more information.
GATE FUSE OK
External Power Supply fuse OK LED
This LED is illuminated when the fuse is “OK”. See
for more information.
GATE POWER
Gate power systems OK LED
This LED is illuminated when all onboard systems are functioning
normally. See
for more information.
POWERFLEX DC SAR GATE
INPUT
PowerFlex DC Stand Alone Regulator Gate Input
Input for the PowerFlex DC Stand Alone Regulator (SAR) Gates.
See
POWERFLEX DC SAR GATE INPUT on page 50
for more
information.
SD3000 PLUS FWD GATE
INPUT
SD3000
PLUS Forward Gate Input
Input for the SD3000
PLUS forward gates. See
for more information.
SD3000 PLUS REV GATE
INPUT
SD3000
PLUS Reverse Gate Input
Input for the SD3000
PLUS reverse gates. See
for more information.
RDY
Normally Open relay contacts
Used to indicate that the Gate Amplifier is “ready to run.” See
for more information.
EXT GATE P/S
External Gate Power Supply
This input is used to increase the gate driver level. See
for more information.
FWD - GATES
Armature Forward Gates
Four forward gate outputs to provide gate signals for up to four
power modules. See
FWD - GATES and REV - GATES on page 52
for more information.
REV - GATES
Armature Reverse Gates
Four reverse gate outputs to provide gate signals for up to four
power modules. See
FWD - GATES and REV - GATES on page 52
for more information.
120VAC
Power Input to Gate Amplifier
Cabinet control power. See
for more
information.
1
2
3
4
5
6
7
8
9