24. Fire the unit to ensure correct operation and flame picture. Ensure the Split Valve and Flame Modulation works as described in the

operations section of this manual.

25. Check the pilot flame that it is the correct size and orientation. The pilot flame can be

adjusted with the adjustment provision on the front face of the valve. This is located just up
and to the left of the regulator motor. It is clearly marked on the valve. Adjusting the screw
in or out will raise or lower the pilot flame height. The correct pilot flame should resemble
Figure 60.

The ignition sequence should be as follows:

a) Press the ON button on the remote control.
b) The receiver should beep, to indicate the command has been received.
c) Within a 2-3 second of the beep, the ignitor should begin to spark. The ignitor will

spark at intervals of 1 second(s).

d) The main valve will open 4-6 seconds after the pilot is lit.
e) Within 4 seconds of the main valve opening, all of the burner ports should light and

remain burning.

26. To complete the LP conversion of this appliance, place the “LP Converted” sticker, supplied

with the LP conversion kit on the rating plate indicating that this unit has been converted
to operate on LP gas.

Figure 59: Pressure Test Points.

Figure 60: Relationship between ignitor and burner.

42

Regency L965E / HZ965E Gas Fireplace