• 50 feet (15.25m) of cable is supplied with this kit, if more venting is required, use 50-2104 - 100 feet (30.5m) PVK CABLE and connect it as shown on
the wiring diagram in Figure 4.
• Allow for an extra 24”-30” (60-75cm) of cable at the PVK control box for future servicing.

2. Reduce the venting size from 5” x 8” to 4” x 6⅝” with a vent reducer, see Figure 1.

3. Using the dimensions in Figures 4 & 5, frame an opening for the thimble of 14½” x 14½” (368mm x 368mm).

4. Insert a 2 ft (61cm) length of the power vent electrical cord through the bushing on the bottom left of the inner thimble, shown in Figure 6.

5. Secure the inner thimble to the wall board with screws.

6. Insert the rest of the power vent electrical cord through the bushing on the right bottom of the outer thimble, refer to Figure 7

39

1

/

16

" (992mm)

44" (1.11m)

9

7

/

16

"

(240mm)

14

1

/

8

"

(359mm)

5" x 8"

90o

Elbow

1ft (305mm)

4" x 6" Vent

5" x 8" to

4" x 6

5

/

8

"

Vent Reducer

Wall

Thimble

Power Vent

Control Box

Power

Vent

Wall

Board

2" x 4"

Wall Stud

Figure 4 Typical overall dimensions with minimum horizontal

vent installed.

14

1

/

2

"

(368mm)

14

1

/

2

"

(368mm)

Figure 5: Thimble framing dimensions.

Regency L965E / HZ965E Gas Fireplace

31

INSTALLATION