Com2 settings, Network address – SATEC RDM172 Manual User Manual
Page 46
![background image](/manuals/572137/46/background.png)
Chapter 3 Display Operations
Menu Operations
46
Series PM172 Powermeters
Label Parameter
Options
Default
Description
Addr
Device address SATEC ASCII: 0-99
Modbus RTU: 1-247
DNP3: 0–65532
DTE: 1-65532
Profibus DP: 0-126
1 (126 for
Profibus)
Device network address
bAud
Baud rate
300-115200 bps
19200 bps The port baud rate
dAtA
Data format and
parity
7E, 8N, 8E
8N
7E data format should
not be used with the
Modbus RTU and DNP3
protocols
H.Sh
Handshaking
(flow control)
nonE=no flow control
SOFt=software
(XON/XOFF)
HArd=hardware (CTS)
None
rtS
RTS mode
nonE = not used
Forc = RTS is
permanently asserted
CtrL = RTS is asserted
during the
transmission
None
1
The meter automatically detects a replaceable communication module and does
not allow you to change the interface, baud rate or data format for the Dial-up
modem, and for the Ethernet or Profibus port.
2
Selecting the DNP3 protocol on the Ethernet port launches the DNP3/TCP server
along with the Modbus/TCP server allowing simultaneous connections on both TCP
ports. Selecting the Modbus protocol for the port disables the DNP3/TCP server.
COM2 Settings
Label Parameter
Options
Default
Description
Prot Communications
protocol
ASCII = SATEC ASCII
rtu = Modbus RTU
dnP3 = DNP3
dtE = DTE
Modbus
RTU
The communications
protocol supported by
the port
rS Port
interface
485 = RS-485
422 = RS-422
RS-485
Addr Device
address
SATEC ASCII: 0-99
Modbus RTU: 1-247
DNP3: 0–65532
DTE: 1-65532
1
Device network address
bAud
Baud rate
300-115200 bps
19200 bps The port baud rate
dAtA
Data format and
parity
7E, 8N, 8E
8N
7E data format should
not be used with the
Modbus RTU and DNP3
protocols
Network Address
This menu allows you to configure the device IP address and the default
gateway address for the Ethernet port. To enter the menu, select “nEt” from
the Main menu, and then press the ENTER button.
To change the IP Address and Default Gateway:
1. To change the device IP address, select the “A” entry in
the upper window with the UP and DOWN arrow buttons.
To change the default gateway address, select the “G”
entry.
2. Press the SELECT button to activate the first address
digit.
3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining address digits.
A.
192.
000.203
168.
G.
192.
000.001
168.