Appendix c setpoint triggers and actions, Setpoint actions, Series pm172 powermeters – SATEC RDM172 Manual User Manual
Page 125
![background image](/manuals/572137/125/background.png)
Appendix C Setpoint Triggers and Actions
Series PM172 Powermeters
125
Display Code
Designation
Description
Mon MONTH
Month
M.dAY
DAY OF MONTH
Day of month
hour HOURS
Hours
Min MINUTES Minutes
SEc SECONDS Seconds
Inter.
MINUTE INTERVAL
Minute interval (1,2,3,4,5,10,15,20,30,60 min)
Event Flags
EH
FG1.On
EVENT FLAG 1 ON
Event flag #1 ON
… …
…
FG8.OFF
EVENT FLAG 8 OFF
Event flag #8 OFF
Setpoint Status
SP1.On
SP 1 ON
Setpoint #1 ON
… …
…
SP16.On
SP 16 ON
Setpoint #16 ON
1
In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to-neutral; for
any other wiring mode, they will be line-to-line voltages.
2
In 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 and 3BLL3 wiring modes, the voltages will be
line-to-neutral; for any other wiring mode, they will be line-to-line.
Setpoint Actions
Display Code
Designation
Description
none
NONE
None (no action)
rEL.1
OPERATE RELAY #1
Operate RO1
rEL.2
OPERATE RELAY #2
Operate RO2
rEL1.OFF
RELEASE RELAY #1
Release latched RO1
rEL2.OFF
RELEASE RELAY #2
Release latched RO2
ELoG EVENT
LOG
Log to Event Log
E
dLoG.1
DATA LOG #1
Log to Data Log file #1
E
dLoG.2
DATA LOG #2
Log to Data Log file #2
E
dLoG.3
DATA LOG #3
Log to Data Log file #3
E
dLoG.4
DATA LOG #4
Log to Data Log file #4
E
dLoG.5
DATA LOG #5
Log to Data Log file #5
E
dLoG.6
DATA LOG #6
Log to Data Log file #6
E
dLoG.7
DATA LOG #7
Log to Data Log file #7
E
dLoG.8
DATA LOG #8
Log to Data Log file #8
E
32.LoG
WAVEFORM LOG #1
Log to Waveform Log file #1
EH
128.LoG
WAVEFORM LOG #2
Log to Waveform Log file #2
EH
Inc.Cn.1
INC CNT #1
Increment counter #1
Inc.Cn.2
INC CNT #2
Increment counter #2
Inc.Cn.3
INC CNT #3
Increment counter #3
Inc.Cn.4
INC CNT #4
Increment counter #4
CLr.Cn.1
CLR CNT #1
Clear counter #1
CLr.Cn.2
CLR CNT #2
Clear counter #2
CLr.Cn.3
CLR CNT #3
Clear counter #3
CLr.Cn.4
CLR CNT #4
Clear counter #4
CLr.Cnt
CLR ALL CNT
Clear all counters
CLr.Enr CLR
ENERGY
Clear total and phase energy accumulators
E
CLr.dnd
CLR ALL DMD
Clear all maximum demands
E
CLr.P.dn
CLR PWR DMD
Clear power maximum demands
E
CLr.A.dn
CLR VOLT/AMP/THD DMD Clear volt, ampere and THD maximum
demands
CLr.tEn
CLR TOU ENG
Clear TOU energy accumulators
E
CLr.tdn
CLR TOU DMD
Clear TOU maximum demands
E
CLr.LHi
CLR MIN/MAX
Clear Min/Max log
FLG1.On
SET FLAG #1
Set event flag #1
EH
FLG2.On
SET FLAG #2
Set event flag #2
EH
FLG3.On
SET FLAG #3
Set event flag #3
EH
FLG4.On
SET FLAG #4
Set event flag #4
EH
FLG1.OFF
CLR FLAG #1
Clear event flag #1
EH
FLG2.OFF
CLR FLAG #2
Clear event flag #2
EH
FLG3.OFF
CLR FLAG #3
Clear event flag #3
EH
FLG4.OFF
CLR FLAG #4
Clear event flag #4
EH