Device options – SATEC RDM172 Manual User Manual
Page 43
![background image](/manuals/572137/43/background.png)
Chapter 3 Display Operations
Menu Operations
Series PM172 Powermeters
43
Label Parameter Options
Default
Description
ConF Wiring
connection
(configuration) mode
See “Basic
Meter
Setup” in
Chapter 4
4Ln3
The wiring connection of the
device
Pt
PT ratio
1.0-6500.0 1.0
The phase potential
transformer’s primary to
secondary ratio
Pt.F
PT Ratio multiplier
Ч1, Ч10
Ч1
PT Ratio multiplication factor.
Used in extra high voltage
networks to accommodate the
PT ratio for 500 kV and higher
networks.
U.SEC Nominal
secondary
voltage
EH
10-690 V
120 V
The nominal secondary line-to-
neutral or line-to-line voltage.
Used as a reference voltage for
the disturbance monitor.
Ct
CT primary current
1-20,000 A 5 A
The primary rating of the phase
current transformer
d.P
Power block demand
period
E
1, 2, 3, 5,
10, 15, 20,
30, 60 min,
E=external
sync
15 min
The length of the demand
period for power demand
calculations. If the external
synchronization is selected, a
pulse front on the digital input
DI1 denotes the start of the
demand interval.
nd.P
The number of blocks in
the sliding window
E
1-15
1
The number of blocks to be
averaged for sliding window
demands
Ad.P
Ampere, volt and THD
demand period
0-1800 sec 900 sec
The length of the demand
period for ampere, volt and
THD demand calculations
Freq Nominal
frequency 50,60,25,
400 Hz
60 Hz
The nominal line frequency
LoAd
Maximum demand load
current
0-20,000 A 0
The maximum demand load
current (0 = CT primary)
Ì
Always specify the wiring mode and transformer ratings prior to setting up
setpoints and analog outputs.
Ì
The maximum value for the product of the phase CT primary current and PT ratio
is 57,500,000. If the product is greater, power readings are zeroed.
Device Options
This menu allows you to change the user-configurable device options or put
the meter into energy test mode. To enter the menu, select the “OPtS” entry
from the Main menu, and then press the ENTER button.
To select a setup option:
1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the
desired option.
To change the option:
1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the
desired option.
3. Press ENTER to confirm your changes and to store your
new setting, or press ESC to discard changes.
To exit the menu, press ESC.
OPtS
rEAc
P.cAL