Electrical installation
Regenerative power supply modules EMB9341 and EMB9342
Power connections
l
113
EDBMB9340 DE/EN/FR 12.0
Wiring procedure
1. Disengage the two covers of the regenerative power supply module to the front
with a slight pressure and remove them.
2. Mount the fixing brackets for the shield sheet
2:
– Hand−screw nut M5
1 on the PE stud 0.
– Fit fixing bracket for shield sheet
2
– Fit serrated lock washer
3
– Fit PE core with ring cable lug
4
– Fit washer
5
– Fit spring washer
6
– Screw on nut M5
7 and tighten with 3.4 Nm (30 lb−in)
3. Use two screws M4 to screw the shield sheet
8 on the fixing bracket.
– Tightening torque 1.7 Nm (15 lb−in)
4. Connect the mains cable
9 to the screw terminals L1, L2, L3 and PE of the mains
filter:
– Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
5. Connect the supply cable of the regenerative power supply module
::
– Connect the screw terminals L1’, L2’, L3’, PE at the mains filter with the screw
terminals L1, L2, L3, PE at the regenerative power supply module in correct phase
relation.
– Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)
– For complying with existing standards (e.g. EN 50178, IEC 61800−3) use shielded
cables from a cable length of 30 cm. Clamp the shield with the clip of the shield
sheet.
6. Connect the supply cable for the controller in the DC−bus connection
; to the screw
terminals +UG, −UG:
– Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in).
7. Wiring of mains synchronisation:
– Internal mains synchronisation: factory−set bridges
<
– External mains synchronisation: remove bridges
< and connect mains
synchronisation cable
=.
– Tightening torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in).
8. Plug the two covers of the power connections on the regenerative power supply
module.