Lenze MC3000 Series User Manual
Page 58

54
13435743_EDBM301_v14 .0
30
CONTROL
(START/STOP CONTROL)
This parameter selects the START/STOP control source, which is either the keypad
(LOCAL), the terminal strip (REMOTE), or the serial link (SERIAL) . The LOCAL/REMOTE
key on the keypad is also affected by the setting of this parameter . The following settings
are possible:
LOCAL
The drive will only respond to START/STOP commands from the keypad .
The LOCAL/REMOTE key is disabled .
REMOTE
The drive will only respond to START/STOP commands from the terminal
strip . The LOCAL/REMOTE key is disabled .
SERIAL
The drive will only respond to START/STOP commands through the serial
link .
kEYPAD
The LOCAL/REMOTE key on the keypad is enabled and is used to toggle
between LOCAL and REMOTE modes . Press the LOCAL/REMOTE key
to select the desired mode and then press the ENTER key within three
seconds .
NOTE: If LOCAL mode is selected, a jumper is required between TB-1
and TB-2 to allow the drive to START .
TB STRIP
The terminal strip is used to select LOCAL or REMOTE mode . LOCAL mode
if TB-13A or TB-13C is set for LOCAL SELECT and a contact closure is
made between TB-13A or TB-13C and TB-2 . If the contact closure is not
made, the drive will be in REMOTE mode .
kEYPAD 2
Acts the same as kEYPAD, but TB-1 is disabled as a STOP input when in
LOCAL mode . Therefore, a jumper is not required between TB-1 and TB-2
to START in LOCAL mode .
NOTE 1:
The STOP key on the keypad is always active . The STOP
input at TB-1 is active unless CONTROL is set to kEYPAD
2 and LOCAL mode is selected .
NOTE 2:
Refer to Parameter 70 - PID MODE for information on the
effects of LOCAL and REMOTE mode when operating the
drive in PID mode .
31
UNITS
(SPEED/PID UNITS)
This parameter sets the units of the output speed or the PID display on the keypad . The
following choices are available:
sp HERTZ
pid CFM
(cubic feet per minute)
sp RPM
(revolutions per minute)
pid GPM
(gallons per minute)
sp %HZ
(percent Hertz)
pid IN
(inches)
sp /SEC
(units per second)
pid FT
(feet)
sp /MIN
(units per minute)
pid /SEC
(units per second)
sp /HR
(units per hour)
pid /MIN
(units per minute)
sp GPH
(gallons per hour)
pid /HR
(units per hour)
NONE
(no units displayed)
pid F
(degrees Fahrenheit)
pid %
(percent of PID feedback)
pid C
(degrees Celsius)
pid PSI
(pounds per square inch)
pid MPM
(meters per minute)
pid FPM
(feet per minute)
pid GPH
(gallons per hour)
NOTE:
If one of the “pid” units is selected, but the drive is in MANUAL (open-loop)
speed control mode or PID MODE is DISABLED, the displayed speed units
will default to HERTZ .