13 keypad control – Lenze MC3000 Series User Manual
Page 28

24
13435743_EDBM301_v14 .0
13
kEYPAD CONTROL
The drive can be operated in a number of different ways: keypad (LOCAL), control devices
wired to the terminal strip (REMOTE), serial communications (SERIAL), or combinations
of each . The drive should first be operated from the keypad during initial start-up . Refer
to Sections 14 - CONTROL WIRING, and 18 - DESCRIPTION OF PARAMETERS for
information on remote operation .
13 .1
kEYPAD FUNCTIONS
START/STOP
To start the drive, press the START key . To stop the drive, press
the STOP key .
NOTE 1: A jumper may need to be installed between TB-1 and
TB-2 in order to START the drive in LOCAL mode
(refer to Parameter 30 - CONTROL) .
NOTE 2: The STOP key is active in both LOCAL and REMOTE
modes .
SPEED SETPOINT
To increase the speed setpoint, press the p key . To decrease
the speed setpoint, press the q key .
NOTE: The
p
and q keys are only active if another speed
reference source is not selected .
LOCAL/REMOTE
To toggle between LOCAL and REMOTE mode, press the
LOCAL/REMOTE key to select the desired mode, and then press
the ENTER key within three seconds to confirm the change .
NOTE:
Parameter 30 - CONTROL must be set to kEYPAD
or kEYPAD 2 for this key to be active .
AUTO/MANUAL
To toggle between AUTOMATIC (terminal strip) and MANUAL
(keypad) speed control, press the AUTO/MAN key to select
the desired mode, and then press the ENTER key within three
seconds to confirm the change .
NOTE:
Parameter 28 - AUTO/MAN must be set to A/M LOC
or A/M SPD for this key to be active . Refer to Section
14 - CONTROL WIRING for information on automatic
speed reference sources .
FAULT RESET
Use the STOP key to reset a fault . If the fault condition has
passed, pressing the STOP key will clear the fault and return
the drive to a STOP condition .
NOTE:
If an OUTPUT fault occurs, there will be a 30 second
delay before the fault can be cleared using the STOP
key .