Commissioning, Important codes for quick commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual
Page 181

Commissioning
Important codes for quick commissioning
l
181
EDK82EV903 DE/EN/FR 5.1
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0034*
v
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position of the
function module!
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
2
Bipolar voltage −10 V ... +10 V
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and gain
3
Current 4 ... 20 mA open−circuit monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
C0034*
v
(A)
uSEr
Range of
setpoint
selection
Application I/O
Observe jumper position of the
function module!
1 X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output frequency (C0010)
not effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
4
Current 4 ... 20 mA open−circuit monitored
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
C0037
JOG1
20.00 −650.00
{0.02 Hz}
650.00 JOG = fixed setpoint
Additional fixed setpoints
ðC0440
C0038
JOG2
30.00 −650.00
{0.02 Hz}
650.00
C0039
JOG3
40.00 −650.00
{0.02 Hz}
650.00
C0050*
uSEr
Output
frequency
(MCTRL1−NOUT)
−650.00
{Hz}
650.00 Read only: Output frequency without
slip compensation
C0087
Rated motor
speed
à
300
{1 rpm}
16000
à
Device−dependent
C0088
Rated motor
current
à
0.0
0.1 (A)
650.0
à
Device−dependent
0.0 ... 2.0 x rated output current of the
controller
C0089
Rated motor
frequency
50
10
{1 Hz}
960
C0090
Rated motor
voltage
à
50
{1 V}
500
à
230 V for 230 V controllers,
400 V for 400 V controllers
C0091
Motor cos
а
0.40
{0.1}
1.0
а
Device−dependent
C0119
v
Configuration of
motor
temperature
monitoring (PTC
input) / earth
fault detection
0
0
PTC input inactive
Earth fault detection
active
l
Configure signal output in C0415
l
If several parameter sets are used,
monitoring has to be set
separately for every parameter set.
l
Deactivate earth fault detection if
the earth fault detection is
actuated unintentionally.
l
If the earth fault detection is
activated, the motor starts with a
delay of approx. 40 ms after
controller enable has been set.
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input inactive
Earth fault detection
inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected