Commissioning, Important codes for quick commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual
Page 180

Commissioning
Important codes for quick commissioning
l
180
EDK82EV903 DE/EN/FR 5.1
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0010
uSEr
Minimum
output
frequency
0.00
0.00
à
14.5 Hz
{0.02 Hz}
650.00
l
C0010 not effective in the case of
bipolar setpoint selection (−10 V ...
+ 10 V)
l
C0010 only limits the analog input
1
l
In the case of a max. output
frequency > 50 Hz the switching
threshold of the auto DCB in C0019
has to be increased.
l
From software 3.5: If
C0010 > C0011, the drive does not
start when controller enable is set.
à
Speed setting range 1 : 6 for Lenze
geared motors: For operation with
Lenze geared motors has to be set
necessarily.
C0011
uSEr
Maximum
output
frequency
50.00 7.50
à
87 Hz
{0.02 Hz}
650.00
C0012
uSEr
Acceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change 0 Hz ...
C0011
l
Additional setpoint
ðC0220
l
Acceleration times that can be
activated via digital signals
ð
C0101
C0013
uSEr
Deceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change C0011...
0 Hz
l
Additional setpoint
ðC0221
l
Deceleration times that can be
activated via digital signals
ð
C0103
C0014
v
Operating mode
2
2
V/f characteristic control V ~ f
(linear characteristic with constant V
min
boost)
l
Commissioning is possible without
identifying motor parameters
l
Advantage of identification with
C0148:
– Improved smooth running at low
speeds
– V/f rated frequency (C0015) and
slip (C0021) are calculated and
saved. They do not have to be
entered
3
V/f characteristic control V ~ f
2
(square−law characteristic with constant
V
min
boost)
4
Vector control
In the case of the first selection enter
the motor data and identify them
with C0148
Otherwise commissioning is not
possible
When C0014 = 5, C0019 must be set =
0 (automatic DC injection brake is
deactivated)
5
Sensorless torque control with speed
limitation
l
Torque setpoint via C0412/6
l
Speed limitation via setpoint 1
(NSET1−N1) if C0412/1 is assigned,
otherwise via maximum frequency
(C0011)
C0015
uSEr
V/f rated
frequency
50.00 7.50
{0.02 Hz}
960.00
l
C0015 is calculated and saved
during the motor parameter
identification with C0148.
l
The setting applies to all permitted
mains voltages
C0016
uSEr
V
min
boost
а
0.00
{0.01 %}
40.00
а
device−dependent
Setting applies to all permitted mains
voltages