Parameter setting with e82zbc keypad, Commissioning – Lenze E82EV 8200 vector 15kW-90kW User Manual
Page 168

Commissioning
Parameter setting with E82ZBC keypad
l
168
EDK82EV903 DE/EN/FR 5.1
7.2
Parameter setting with E82ZBC keypad
,
Read the documentation for the keypad before starting work!
After every mains switching, or after connection of the keypad during operation, the 10
codes that have been defined in code C0517 are immediately available.
By default, the user menu contains all codes required for commissioning a standard
application with linear V/f characteristic control:
Code
Designation
Lenze setting
C0050
Output frequency
Display: output frequency without slip compensation
C0034
Range of setpoint selection
0
Standard I/O
X3/8: 0 ... 5 V / 0 ... 10 V / 0 ... 20 mA
Application I/O
X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V
C0007
Fixed configuration digital
inputs
0
E4
E3
E2
E1
CW/CCW
DCB
JOG2/3
JOG1/3
Clockwise
rotation/counte
r−clockwise
rotation
DC injection
brake
Selection fixed setpoints
C0010
Minimum output frequency
0.00 Hz
C0011
Maximum output frequency
50.00 Hz
C0012
Acceleration time main
setpoint
5.00 s
C0013
Deceleration time main
setpoint
5.00 s
C0015
V/f rated frequency
50.00 Hz
C0016
V
min
boost
device−dependent
C0002
Parameter set management
Re−establish delivery status; transfer parameter sets by
means of the keypad; save, load, or copy own basic settings
)
Note!
Via C0002 "Parameter set transfer/establishing the delivery status", you can
transfer configurations from drive controller to drive controller by means of
the keypad, or re−establish the delivery status by loading the Lenze setting
(e. g. if you’ve lost track during parameterising).