Feldbus-baugruppe 2113 interbus – Lenze EMF2113IB User Manual
Page 76

Data transfer
Process data preconfiguration depending on L-C0009
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.3
L
7.6-25
EDSIBS-1.0-06/2003
Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 14 (e.g. via keypad)
2. Set L C0009
14 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations DCSTW
and DCG.
•
The process data length (PD) is set to 2 words by L-C1910 = 4.
•
DRIVECOM is activated with L-C1911 = 1.
Acceptance of settings
The fieldbus module must be switched on again to activate the process
data word length.
Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 25 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations GSTW,
AIF-W1, AIF-W2.
•
The process data length (PD) is set to 3 words by L-C1910 = 6.
•
DRIVECOM is activated by L-C1911 = 0.
Acceptance of settings
The fieldbus module must be switched on again to activate the process
data word length.
Example 3: DRIVECOM control with 5 process data words (e.g. configuration L-C0009 = 21)
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 21 (e.g. via keypad)
3. DIP switch
– S1 = OFF, S2 = ON, S3 = OFF, S4 = ON (PD = 5 words)
– S5/S6: Set required PCP data word length
– S7 = ON (DRIVECOM activated)
4. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations DCSTW,
DCG, AIF-W2, AIF-W3, AIF-W4.
•
Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active
(DIP switch in position “ON”).
Acceptance of settings
A process data word length of 5 words and DRIVECOM are immediately
active through switches.
Example 4: Configuration of 10 PD words to AIF interface (configuration L-C0009 = 27).
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 27 (e.g. via keypad)
3. DIP switch
– S1 = ON, S2 = OFF, S3 = ON, S4 = OFF (PD = 10 words)
– S5 = OFF, S6 = OFF: no PCP
– S7 = OFF (DRIVECOM deactivated)
4. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations
AIF-W1 .... AIF-W10.
•
Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active
(DIP switch in position “ON”).
Acceptance of settings
All switch settings become active immediately.
Examples for process data
preconfiguration