Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-22
EDSIBS-1.0-06/2003
The following data can be assigned to the PA data:
Index Subindex Name/variable name
Explanation
Lenze setting: Index 6001
hex
6040 0
DRIVECOM control word
PO data word 1
6042 0
DRIVECOM speed setpoint
Speed setpoint [rpm] PO data word 2
6052 0
DRIVECOM percentage setpoint
Speed setpoint [%]
5F78 0
Device control word (AIF1_wDctrlCtrl)
5CA7 1
AIF1_nInW1_a
AIF word 1
5CA7 2
AIF1_nInW2_a
AIF word 2
PO data word 3
5CA7 3
AIF1_nInW3_a
AIF word 3
PO data word 4
5CA7 4
AIF2_nInW1_a
AIF word 4
PO data word 5
5CA7 5
AIF2_nInW2_a
AIF word 5
PO data word 6
5CA7 6
AIF2_nInW3_a
AIF word 6
PO data word 7
5CA7 7
AIF2_nInW4_a
AIF word 7
PO data word 8
5CA7 8
AIF3_nInW1_a
AIF word 8
PO data word 9
5CA7 9
AIF3_nInW2_a
AIF word 9
PO data word 10
5CA7 10
AIF3_nInW3_a
AIF word 10
5CA7 11
AIF3_nInW4_a
AIF word 11
5CA6 0
AIF1_dnInD1_p
AIF double word 1
)
)
)
)
Note!
9300 Servo PLC
Please execute the following logic operations in the PLC program
of the controller:
AIF1_wDctrlCtrl
W DCTRL_wAIF1Ctrl
DCTRL_wStat
W AIF1_wDctrlStat
Drive PLC
It is necessary to use the device control for the Drive PLC.
Process data telegram to drive