beautypg.com

Buderus, G615, Series boiler – Beckett BRYAN STEAM CF2500A User Manual

Page 4

background image

Buderus

G615

Series Boiler

Boiler

Burner

Chassis

Spec.

Air Tube

Combination

High

Fire
Rate

Nozzle

Head

Setting

Blue -

Low Fire

Air or

Shutter

Red -

High Fire

Air or

Band

Low Fire

Pump

Press.

High Fire

Pump

Press.

Pressure

Firing
Flange

Insertion

9

CF2300A

BCF304

CF102KG

16.00

9.00x45P

5

30

60

150

300

51630

6.25"

10

CF2500

BCF1801

CF102KP

18.50

5.00x45P (2)

2

23

25

300

300

51630

6.25"

11

CF2500

BCF1801

CF102KP

21.00

6.00x45P (2)

5

27

40

300

300

51630

6.25"

12

CF3500A

BCF1301

CF114KM

23.50

6.50x45P (2) 4-1/2

20

35

300

300

51630

6.25"

13

CF3500A

BCF1301

CF114KM

26.00

7.50x45P (2)

5

25

40

300

300

51630

6.25"

14

CF3500

BCF1301

CF114KR

28.50

8.50x60P (2)

6

30

60

300

300

51631

6.25"

Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.

Flange requires an additional adapter plate.

Page 3