Beckett CG10 User Manual
Cg10, Beckett, Specifi cations

www.beckettcorp.com
R.W. Beckett Corporation ● Elyria, Ohio
Specifi cations
Input fi ring range 300 to 1200 MBh
Fuel Natural gas - 0.6 specifi c gravity typical
Gas train Standard: UL listed/CSD-1 Confi guration
Options: IRI and FM
Manifold pressure 1.0 to 4.6 inches W.C. typical
Firing mode On/Off or On/Off with Low Fire Start
Flame safeguard RM7895A Standard (Options available)
Flame detection Standard: Flame rod rectifi cation
Optional: Ultraviolet scanner
Air proving switch Standard
Gas pressure
switches
Standard high and low
Ignition Direct spark main fl ame
Motor Standard: 1/3 HP; 3450 RPM; 120 volt/60 hz,
single phase
Optional motor: 50 or 60 hz (see notice for 50
hz), 240 volt single phase
Weight 55 lbs.
Features
S - Standard O - Optional N/A - Not Available
On/Off with Low Fire Start
S
Propane Restrictor
O
Linkageless Low/High/Low or Low/High/Off
N/A
Modulation with Pressure/Temperature Modulating Controller
N/A
Right or Left Side Gas Train Connection
S
Air Pressure Switch
S
Low Gas Pressure Switch
S
High Gas Pressure Switch
S
Main Shutoff Cock, Leak Test Cock, Test Connections, and Test Cocks
S
Direct Spark Ignition of Main Flame
S
Flame Safeguard with Flame Rod
O
Flame Safeguard with UV Sensor
S
Customized Electrical Cabinet
O
UL/CUL - CSD1 - Swiss Re
S
FM
O
IRI (old standard)
O
Power On - Fuel On, Indicator Light
O
11.7
6.0
8.1
4.4
4.6
25.5
6.8
8.2
9.9-11.0
Overall Dimensions
Gas Gun Assembly
BECKETT
CG10
COMMERCIAL GAS BURNER
Gas Train Assembly (Typical Gas Train, other confi gurations are available)
LGPS
TC
TC
HGPS
MSC
U
SSOV1
2PRSSOV
MLTC
U
TP