Weil mclain, Series boiler – Beckett BRYAN STEAM CF2500A User Manual

Page 34

background image

Weil McLain

88-2

Series Boiler

Boiler

Burner

Chassis

Spec.

Air Tube

Combination

High

Fire
Rate

Nozzle

Head

Setting

Blue -

Low Fire

Air or

Shutter

Red -

High Fire

Air or

Band

Low Fire

Pump

Press.

High Fire

Pump

Press.

Pressure

Firing
Flange

Insertion

488

CF1400 BCF205 CF66KD 7.00

04.00x70B(D

)

4

39

54

150

300

0

4.00"

588

CF2300A

BCF304

CF66KG

9.40

05.50x60P

0

34

42

150

300

0

4.00"

688

CF2300A

BCF304 CF66KG 11.80

07.00x60B(D

)

3

41

51

150

300

0

4.00"

788

CF2300A

BCF304 CF66KG 14.20

08.50x60B(D

)

6

43

54

150

280

0

4.00"

888

CF2500A

BCF3001

CF66KP

16.60

05.00x45PLP

2

24

50

300

300

0

4.00

988

CF2500A

BCF3001

CF66KP 18.80

05.50x60P(H

) 4.00

27

52

300

0

4.00"

1088

CF2500 BCF1801

CF66KP 21.50

06.50x60B(D

)

8

28

54

300

0

4.00"

1188

CF2500 BCF1801

CF66KP 23.50

07.00x45B(D

)

8

29

44

300

0

4.00"

1288

CF3500A

BCF1301

CF80KM 26.00

07.50x45B(D

)

3

31

63

300

0

4.50"

1388

CF3500A

BCF1301

CF80KM 28.50

08.50x45B(D

)

6

33

98

300

0

4.50"

Shutter and band settings refer to the AFG, CF375, CF500 and CF800 only.

0.5 DEGREE PITCH