Bryant Deluxe 4 WAy Gas Furnase 355MAV User Manual
Page 53

j. Remove jumpers R to W/W1 and R to W2.
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas
meter.
a. Calculate high-altitude adjustment (if required).
CAUTION: DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame impingement of burners and heat exchangers, causing failures.
(See Fig. 57.)
UNITED STATES
At altitudes above 2000 ft, this furnace has been approved for a 2 percent derate for each 1000 ft above sea level. See Example and Table 14 for
derate multiplier factor.
Table 13—Model 355MAV Orifice Size and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 20,000 Btuh High Heat/13,000 Btuh Low Heat per Burner, Derated 2 Percent for Each 1000 ft Above
Sea Level)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
4001
to
5000
725
43
3.7/1.5
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
42
3.4/1.4
750
44
3.4/1.4
43
3.5/1.5
43
3.7/1.5
43
3.8/1.6
42
3.2/1.4
775
44
3.7/1.6
44
3.8/1.6
43
3.4/1.4
43
3.5/1.5
43
3.7/1.5
800
44
3.5/1.5
44
3.6/1.5
44
3.7/1.6
44
3.8/1.6
43
3.4/1.4
825
44
3.2/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
44
3.7/1.6
850
45
3.7/1.6
45
3.8/1.6
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
875
45
3.5/1.5
45
3.6/1.5
45
3.7/1.6
44
3.2/1.3
44
3.3/1.4
900
45
3.3/1.4
45
3.4/1.4
45
3.5/1.5
45
3.6/1.5
45
3.8/1.6
925
47
3.7/1.6
45
3.2/1.4
45
3.3/1.4
45
3.4/1.5
45
3.6/1.5
950
47
3.5/1.5
47
3.6/1.5
45
3.2/1.3
45
3.3/1.4
45
3.4/1.4
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
and
Canada
5001
to
6000
700
43
3.6/1.5
43
3.7/1.6
42
3.2/1.3
42
3.3/1.4
42
3.4/1.4
725
43
3.4/1.4
43
3.5/1.5
43
3.6/1.5
43
3.7/1.6
43
3.8/1.6
750
44
3.6/1.5
44
3.7/1.6
43
3.4/1.4
43
3.5/1.5
43
3.6/1.5
775
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
44
3.7/1.6
43
3.4/1.4
800
44
3.2/1.3
44
3.3/1.4
44
3.4/1.4
44
3.5/1.5
44
3.6/1.5
825
45
3.6/1.5
45
3.7/1.6
44
3.2/1.4
44
3.3/1.4
44
3.4/1.4
850
45
3.4/1.4
45
3.5/1.5
45
3.6/1.5
45
3.8/1.6
44
3.2/1.4
875
45
3.2/1.4
45
3.3/1.4
45
3.4/1.5
45
3.6/1.5
45
3.7/1.5
900
47
3.6/1.5
47
3.7/1.6
45
3.3/1.4
45
3.4/1.4
45
3.5/1.5
925
47
3.4/1.4
47
3.5/1.5
47
3.7/1.5
45
3.2/1.3
45
3.3/1.4
950
48
3.7/1.6
48
3.8/1.6
47
3.5/1.5
47
3.6/1.5
47
3.7/1.6
975
48
3.5/1.5
48
3.6/1.5
48
3.8/1.6
47
3.4/1.4
47
3.5/1.5
1000
48
3.3/1.4
48
3.5/1.5
48
3.6/1.5
48
3.7/1.6
48
3.8/1.6
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58
0.60
0.62
0.64
0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A.
Only
6001
to
7000
650
42
3.2/1.3
42
3.3/1.4
42
3.4/1.4
42
3.5/1.5
42
3.6/1.5
675
43
3.6/1.5
43
3.7/1.6
43
3.8/1.6
42
3.2/1.4
42
3.3/1.4
700
44
3.8/1.6
43
3.4/1.5
43
3.6/1.5
43
3.7/1.6
43
3.8/1.6
725
44
3.6/1.5
44
3.7/1.6
44
3.8/1.6
43
3.4/1.4
43
3.5/1.5
750
44
3.3/1.4
44
3.4/1.5
44
3.6/1.5
44
3.7/1.6
44
3.8/1.6
775
45
3.8/1.6
44
3.2/1.4
44
3.3/1.4
44
3.4/1.5
44
3.5/1.5
800
45
3.5/1.5
45
3.7/1.5
45
3.8/1.6
44
3.2/1.4
44
3.3/1.4
825
45
3.3/1.4
45
3.4/1.5
45
3.6/1.5
45
3.7/1.6
45
3.8/1.6
850
47
3.7/1.6
45
3.2/1.4
45
3.4/1.4
45
3.5/1.5
45
3.6/1.5
875
47
3.5/1.5
47
3.6/1.5
45
3.2/1.3
45
3.3/1.4
45
3.4/1.4
* Orifice numbers 45 are factory installed.
—53—