Bryant Deluxe 4 WAy Gas Furnase 355MAV User Manual

Page 36

background image

If use of this drain connection is desired, drill out fitting’s tap plug with a 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should

be routed to open condensate drain for furnace and A/C (if used), and should be trapped. (See Fig. 38.)

2. Attach vent pipe to furnace as follows:

a. Determine location of vent pipe connection to inducer housing as shown in Fig. 36 for application.
b. Reposition elastomeric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connection. Tighten clamp.

WARNING: Inducer housing outlet cap must be installed and fully seated against inducer housing. Clamp must be

tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal

injury, or death.

c. Install pipe support (factory-supplied in loose parts bag) into selected furnace casing vent pipe hole. Pipe support should be positioned

at bottom of casing hole.

Table 7—Maximum Allowable Pipe Length (ft) (Continued)

ALTITUDE (FT)

UNIT SIZE

TERMINATION

TYPE

PIPE DIA

(IN.)*

NUMBER OF 90° ELBOWS

1

2

3

4

5

6

8001 to 9000‡

042040

2 Pipe or 2-in

Concentric

1-1/2

30

25

20

15

10

5

2

62

60

58

56

55

53

042060

2 Pipe or 2-in

Concentric

1-1/2

30

25

20

15

10

5

2

62

60

58

56

55

53

042080

060080

2 Pipe or 2-in

Concentric

1-1/2

17

12

7

NA

NA

NA

2

62

60

58

56

51

46

060100

2 Pipe or 2-in

Concentric

2

27

22

17

12

7

NA

2-1/2

62

60

58

56

55

53

060120

2 Pipe or 3-in.

Concentric

3†

43

41

39

37

35

34

ALTITUDE (FT)

UNIT SIZE

TERMINATION

TYPE

PIPE DIA

(IN.)*

NUMBER OF 90° ELBOWS

1

2

3

4

5

6

9001 to 10,000‡

042040

2 Pipe or 2-in

Concentric

1-1/2

27

22

17

12

7

NA

2

57

55

53

51

49

47

042060

2 Pipe or 2-in

Concentric

1-1/2

27

22

17

12

7

NA

2

57

55

53

51

49

47

042080

060080

2 Pipe or 2-in

Concentric

1-1/2

15

10

5

NA

NA

NA

2

57

55

53

51

46

41

060100

2 Pipe or 2-in

Concentric

2

24

19

14

9

NA

NA

2-1/2

57

55

53

51

49

47

060120

2 Pipe or 3-in.

Concentric

3

39

37

35

33

31

29

Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag)

†Wide radius elbow.

‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction.

NA-Not Allowed; pressure switch will not make.

NOTES:

1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.

2. Size both the combustion-air and vent pipe independently, then use the larger of these two diameters for both pipes.

3. Assume two 45° elbows equal one 90° elbow. Long radius elbows are desirable and may be required in some cases.

4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.

5. The minimum pipe length is 5 ft for all applications.

Fig. 38—Intake Housing Plug Fitting Drain

A93035

COMBUSTION

AIR PIPE

BURNER

BOX

COMBUSTION AIR

INTAKE HOUSING

3/8" ID TUBE

TRAP

TO OPEN

DRAIN

3/16"

DRILL

4″

(102mm)

MIN

—36—