NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 40, 41, 42, 43, and 44.

EXAMPLE: An 042080 size furnace located in Indianapolis, elevation 650 ft above sea level, could be installed in an application requiring

3 elbows and 17 ft of vent pipe, along with 5 elbows and 16 ft of combustion-air pipe. Table 7 indicates this application would allow a

1-1/2-in. diameter vent pipe, but require a 2-in. diameter combustion air pipe (1-1/2-in. pipe is good for 20 ft with 3 elbows, but only 10

ft with 5 elbows). Therefore, 2-in. diameter pipe must be used for both vent and combustion-air pipes since larger required diameter must

always be used for both pipes. If same installation were in Albuquerque, elevation 5250 ft above sea level, installation would require 2-in.

vent pipe and combustion-air pipe. At 5001- to 6000-ft elevation, 1-1/2-in. pipe is not allowed with 5 elbows, but 2-in. pipe is good for

68 ft with 5 elbows.

COMBUSTION-AIR AND VENT PIPE ATTACHMENT
NOTE: All pipe joints must be watertight except attachment of combustion-air pipe to inlet housing connection, since it may be necessary to

remove pipe for servicing.

1. Attach combustion-air pipe to furnace as follows:

a. Determine location of combustion-air intake pipe connection to combustion-air intake housing as shown in Fig. 36 for application.
b. Reposition combustion-air intake housing plug fitting in appropriate unused intake housing connection.
c. If required, insert perforated disk assembly (factory-supplied in loose parts bag) in intake housing where combustion-air intake pipe will

be connected. If half disk set is required, install with shoulder of disk against stop in combustion-air inlet.

d. Install pipe support (factory-supplied in loose parts bag) into selected furnace casing combustion-air pipe hole. Pipe support should be

positioned at bottom of casing hole.

e. Insert 2-in. diameter pipe into intake housing.
f. Install casing hole filler cap (factory-supplied in loose parts bag) in unused combustion-air pipe casing hole.

Table 7—Maximum Allowable Pipe Length (ft)

ALTITUDE (FT)

UNIT SIZE

TERMINATION

TYPE

PIPE DIA

(IN.)*

NUMBER OF 90° ELBOWS

1

2

3

4

5

6

0 to 2000

042040

2 Pipe or 2-in

Concentric

1-1/2

50

45

40

35

30

25

2

70

70

70

70

70

70

042060

2 Pipe or 2-in

Concentric

1-1/2

50

45

40

35

30

25

2

70

70

70

70

70

70

042080

060080

2 Pipe or 2-in

Concentric

1-1/2

30

25

20

15

10

5

2

70

70

70

70

70

70

060100

2 Pipe or 2-in

Concentric

2

45

40

35

30

25

20

2-1/2

70

70

70

70

70

70

060120

2 Pipe or 3-in.

Concentric

2-1/2

10

NA

NA

NA

NA

NA

3

35

30

15

NA

NA

NA

3†

70

70

70

70

70

70

ALTITUDE (FT)

UNIT SIZE

TERMINATION

TYPE

PIPE DIA

(IN.)*

NUMBER OF 90° ELBOWS

1

2

3

4

5

6

2001 to 3000

042040

2 Pipe or 2-in

Concentric

1–1/2

45

40

35

30

25

20

2

70

70

70

70

70

70

042060

2 Pipe or 2-in

Concentric

1–1/2

45

40

35

30

25

20

2

70

70

70

70

70

70

042080

060080

2 Pipe or 2-in

Concentric

1–1/2

26

21

16

11

6

NA

2

70

70

70

70

70

70

060100

2 Pipe or 2-in

Concentric

2

40

35

30

25

20

15

2–1/2

70

70

70

70

70

70

060120

2 Pipe or 3-in.

Concentric

3

31

26

12

NA

NA

NA

3†

63

62

62

61

61

61

ALTITUDE (FT)

UNIT SIZE

TERMINATION

TYPE

PIPE DIA

(IN.)*

NUMBER OF 90° ELBOWS

1

2

3

4

5

6

3001 to 4000

042040

2 Pipe or 2-in

Concentric

1-1/2

42

37

32

27

22

17

2

70

70

70

70

70

70

042060

2 Pipe or 2-in

Concentric

1-1/2

42

37

32

27

22

17

2

70

70

70

70

70

70

042080

060080

2 Pipe or 2-in

Concentric

1-1/2

25

20

15

10

5

NA

2

70

70

70

70

70

70

060100

2 Pipe or 2-in

Concentric

2

38

33

28

23

18

13

2-1/2

70

70

70

70

70

70

060120

2 Pipe or 3-in.

Concentric

3

29

24

10

NA

NA

NA

3†

59

59

58

57

57

56

See notes at end of table.

—34—