NOTE: Remove furnace perforated, supply-air duct flanges when they interfere with mating flanges on coil or downflow subbase. To remove

perforated, supply-air duct flanges, use wide duct pliers, duct flange tool, or hand seamers to bend flange back and forth until it breaks off. Be

careful of sharp edges. (See Fig. 21.)

WARNING: Do not bend duct flanges inward as shown in Fig. 21. This will affect airflow across heat exchangers and

may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum

of 210° as shown in Fig. 21.

PROCEDURE 3—INSTALLATION IN HORIZONTAL APPLICATIONS
These furnaces can be installed horizontally in either horizontal left or right discharge position. In a crawlspace, the furnace can either be hung

from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See

Fig. 22.) Cut hanger bolts (4 each 3/8-in. all-thread rod) to desired length. Use 1 X 3/8-in. flat washers, 3/8-in. lock washers, and 3/8-in. nuts on

hanger rods as shown in Fig. 22. Dimples are provided for hole locations. (See Fig. 2.)

Fig. 18—Floor and Plenum Opening Dimensions

A96283

PLENUM

OPENING

C

A

B

D

FLOOR

OPENING

Fig. 19—Furnace, Plenum, and Subbase Installed

on a Combustible Floor

A96285

DOWNFLOW

SUBBASE

SHEET METAL

PLENUM

FLOOR

OPENING

FURNACE

(OR COIL CASING

WHEN USED)

COMBUSTIBLE

FLOORING

—19—