Bryant Deluxe 4 WAy Gas Furnase 355MAV User Manual

Page 30

background image

NOTE: Furnace combustion-air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing

in vertical pipe. (See Fig. 35.) This allows proper drainage of vent condensate.
Combustion-air and vent pipes must terminate together in same atmosphere pressure zone, either through roof or sidewall (roof termination

preferred), using accessory termination kit. See Table 5 for required clearances.
Furnace combustion-air and vent pipe connections must be attached as shown in Fig. 37. Combustion-air intake plug fitting and inducer housing

alternate vent cap may need to be relocated in some applications.
NOTE: Slope combustion-air and vent pipes a minimum of 1/4 in. per linear ft with no sags between hangers.

CAUTION: When combustion-air pipe is installed above a suspended ceiling, pipe must be insulated with 3/8-in. thick

Armaflex-type insulation. Combustion-air pipe should also be insulated when it passes through warm, humid space.

An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air and vent pipes. Each furnace must

have its own set of combustion-air and vent pipes and be terminated individually, as shown in Fig. 39, 40, 44 and 45.

Fig. 33—355MAV Variable Speed Furnace Control

A99098

SEC-2

SEC-1

DE

W2

Com 24V

W/W1

Y/Y2

HUM

RG

DEHUM

DE CONNECTION

DE CONNECTION

LOCATION

Fig. 34—Thermidistat Connection

A98295

24 VAC HOT

DEHUMIDIFY

24 VAC COMM

R

R

Com

DHUM

DEHUM

C

DE

NOTE 1

THERMIDISTAT

VARIABLE-SPEED

CONDENSING

FURNACE

NOTE 1 - Remove DE Connection
To Enable DEHUM Input

—30—