Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger

every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.

CAUTION: Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls.

WARNING: Gas valve shutoff switch MUST be facing forward or tilted upward. Failure to follow this warning could

result in property damage or death.

WARNING: Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources

of ignition for purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning

could result in fire, explosion, personal injury, or death.

WARNING: Use proper length of pipe to avoid stress on gas control manifold. Failure to follow this warning could

result in a gas leak resulting in fire, explosion, personal injury, or death.

Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section

of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground

joint union between gas control manifold and manual gas shutoff valve. (See Fig. 26.)

CAUTION: If a flexible connector is required or allowed by authority having jurisdiction, black iron pipe shall be

installed at gas valve and extend a minimum of 2 in. outside furnace casing.

An accessible manual shutoff valve MUST be installed upstream of furnace gas controls and within 6 ft of furnace. A 1/8-in. NPT plugged tapping,

accessible for test gage connection, MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual

shutoff valve.

Table 3—Maximum Capacity of Pipe*

NOMINAL

IRON

PIPE

SIZE

(IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE (FT)

10

20

30

40

50

1/2

0.622

175

120

97

82

73

3/4

0.824

360

250

200

170

151

1

1.049

680

465

375

320

285

1-1/4

1.380

1400

950

770

660

580

1-1/2

1.610

2100

1460

1180

990

900

* Cubic ft of gas per hr. for gas pressures of 0.5 psig (14–in. wc) or less and a pressure drop of 0.5–in wc (based on a 0.60 specific gravity gas).

Ref: NFGC.

Fig. 26—Typical Gas Pipe Arrangement

A93324

UNION

SEDIMENT

TRAP

MANUAL

SHUTOFF

VALVE

(REQUIRED)

GAS

SUPPLY

—24—