NOTE: The CF switches are factory set to provide continuous fan airflow equal to low-heat mode.

5. Replace main furnace door and blower access panel.

C. Setup Switches (SW)
The control center has 8 setup switches that may be set to meet the application requirements. Position these setup switches for the appropriate

requirement.

1. Remove main furnace door and blower access panel.

Table 9—Air Conditioning (A/C) Airflow Switch Position

AIR

CONDITIONER

(TONS)

CFM AIRFLOW

A/C SETUP

SWITCH POSITION

ALLOWABLE FURNACE MODEL SETUP

A/C-1

A/C-2

A/C-3

042040

042060

042080

060080

060100

060120

Default

1200 or

2000

OFF

OFF

OFF

3 Tons

1200 CFM

3 Tons

2000 CFM

3 Tons

1200 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

5 Tons

2000 CFM

1–1/2

600

ON

OFF

OFF

X

X

X

2

800

OFF

ON

OFF

X

X

X

X

X

X

2–1/2

1000

ON

ON

OFF

X

X

X

X

X

X

3

1200

OFF

OFF

ON

X

X

X

X

X

X

3–1/2

1400

ON

OFF

ON

X

X

X

X

X

X

4

1600

OFF

ON

ON

X

X

X

5

2000

ON

ON

ON

X

X

X

X–Indicates allowable selection.