Appendix d, Iecex approvals – Det-Tronics U9500 Infiniti Gas Transmitter User Manual
Page 47

95-8444
D-1
10.1
APPENDIX D
IECEx APPROVALS
INFINITI U9500 GAS TRANSMITTER
IECEx ULD 10.0009
Ex d IIC T5-T6 Gb
T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –55°C to +75°C)
IP66
IEC Standards: IEC 60079-0: 2007
IEC 60079-1: 2007
IEC 60529, 2.1.ed.+Corr. 1:2003+2:2007
Read and understand instruction manual before operating.
To obviate the risk of hot spots and capacitor energy storage, the enclosure must not be opened, even when isolated,
when an explosive gas atmosphere is present.
All cable entry devices and blanking elements shall be certified in type of explosion protection flameproof enclosure
“d”, suitable for the conditions of use and correctly installed. Unused apertures shall be closed with suitable certified
blanking elements.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
CATALYTIC COMBUSTIBLE GAS SENSOR (CGS)
IECEx ULD 10.0001X
Ex d IIC T3, T5 Gb
T5 (Tamb = –40°C to +75°C)
T3 (Tamb = –55°C to +125°C)
IEC Standards:
IEC 60079-0: 2007
IEC
60079-1:
2007
CONDITION OF CERTIFICATION:
The CGS Combustible Gas Sensor is certified for use in following ambient temperatures:
- ambient temperature range –40°C to +75°C
Coding:
Ex d
IIC T5 Gb
- ambient temperature range –55°C to +125°C
Coding: Ex d IIC T3 Gb
The actual temperature range is marked on the sensor.
The CGS Combustible Gas Sensor can withstand repeated exposures to 125°C for periods up to 12 hours. It is
recommended that the sensor be replaced after maximum 500 hours of exposed to the 125°C temperature condition.
The CGS Combustible Gas Sensor must only be mounted into the enclosures of the Infiniti Gas Transmitter Model
U9500A Series, the Combustible Gas Transmitter Model 505 Series, the Digital Communication Unit EQ 22xxDCUEX
Series or the Sensor Termination Box Model STB Series.