Appendix a, Fm approval and performance report – Det-Tronics U9500 Infiniti Gas Transmitter User Manual
Page 36

95-8444
A-1
10.1
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
Refer to drawing 006722-001 (Figure A1) for applicable area classification and installation details.
COMBUSTIBLE
Transmitters
: U9500A1001, U9500A1004, with Junction Box P/N 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.
Hydrocarbon Gas Transmitters
: U9500H6002 or U9500H6004, with Junction Box P/N 006264-XXX.
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250. (For use with Sensor Termination box.)
• Performance verified up to 100% LFL methane-in-air atmospheres per FM 6320.
Sensor Termination Box
: Model STB Series, used with Combustible units above:
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
• Dust ignition-proof for Class II/III, Division 1, Groups E, F and G Hazardous (Classified) Locations per FM 3615.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4A); Class II/III, Division 2, Groups F and G (T4A)
Hazardous (Classified) Locations per FM 3611.
• Enclosure Rating NEMA/Type 4X (Indoor/Outdoor) per ANSI/NEMA 250.
Combustible Gas Sensors
: Model CGS:
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous (Classified) Locations per FM 3615.
Hydrocarbon Sensors
:
Model PIR9400:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T5) Hazardous (Classified) Locations.
• Class I, Division 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations, Tamb = –40°C to +75°C, conduit
seal not required.
Model PIRECL:
• Explosion-proof for Class I, Division 1, Groups B, C and D (T4) Ta = 75°C with intrinsically safe output for HART
Communications in accordance with control drawing 0072783-001, conduit seal not required.
• Non-incendive for Class I, Division 2, Groups A, B, C and D (T4) Ta = 75°C Hazardous (Classified) Locations.
Stand-alone 4-20 mA FM Approved Gas Sensor/Transmitter:
• See specific detector rating.