CONTROLLER/SIGNAL RECEIVER OPTIONS
All Model U9500 Series transmitters offer an analog 4

to 20 mA output, which is configurable for electrically

isolated or non-isolated operation. The analog signal is

capable of driving a maximum 600 ohm resistance load.

Typical controllers used with the U9500 Series include

the family of R8471 Controllers, or the Model 8000 eight

channel controller for % LFL flammable gas monitoring.

It is also acceptable to use the U9500 with other devices

or systems capable of accepting 4 to 20 mA signal

inputs. The following illustrations provide examples

of recommended interconnecting wiring between the

U9500 and analog signal receivers:

Figure 11 — A Typical System, Infiniti Transmitter with

PointWatch Wired to R8471 Controller,

Non-Isolated Current Output

Figure 12 — A Typical System, Infiniti Transmitter

with PointWatch Wired to a Model 8000

Controller, Isolated Current Output

Figure 13 — A Typical System, Infiniti Transmitter

used with PLC Analog Input Module,

Isolated/Non-Isolated Current Output

SENSOR SEPARATION
Det-Tronics sensor termination boxes (STBs) enable

the installation of the sensor separately from the Infiniti

transmitter module. Three conductor shielded cable must

be used to prevent possible nuisance EMI/RFI. Contact

the factory for ordering information. (See Appendix C for

CE/ATEX rating details.) Refer to these typical system

wiring diagrams for guidance:

Table 2 — Wiring Size and Maximum Distance from

Transmitter to Sensor

Figure 14 — Sensor Separation with Combustible Gas

Sensor and Infiniti Transmitter

Figure 15 — Sensor Separation with PointWatch and

Infiniti Transmitter

Figure 16 — Sensor Separation with Toxic and

Oxygen Gas Sensors and Infiniti

Transmitter

Figure 17 — Sensor Separation with Chlorine Gas

Sensor, Intrinsically Safe barrier and

Infiniti Transmitter

AUX RELAY LOW RELAY HIGH RELAY

NC COM NO NC COM NO NC COM NO

FLT RELAY

S POWER

RESET

PW

IN

NO COM NC – + CAL

S

POWER OUT

– + + –

BLACK

RED

YELLOW

WHITE

GREEN

POINTWATCH DETECTOR

ISOLATED OUTPUT

CURRENT LOOP

CHASSIS GROUND

POWER

SENSOR

EXTERNAL RESET

HIGH ALARM

HIGH ALARM / OC

AUX. ALARM

AUX. ALARM / OC

LOW ALARM

LOW ALARM / OC

FAULT

FAULT / OC

1

3

4

5

6

7

8

9

10

11

12

13

14

15

16

+

+

+

18 TO 32VDC

GROUND

POWER

SIGNAL

HIGH

ALARM

AUXILIARY

ALARM

LOW

ALARM

FAULT

RESET

24 VDC

+

2

4-20 MA

A2034

R8471 CONTROLLER

*

*

*NO CONNECTION

Figure 11—A Typical System, Infiniti Transmitter with PointWatch Wired to R8471 Controller, Non-Isolated Current Output