2.1

fAuLt RELAy—

Form C Type (NO/NC). Energized during Normal mode,

De-Energized on Fault or loss of power.

Contact Rating: 5 amperes at 30 Vdc.

Non-Latching Operation only — not programmable.

DIGItAL outPut (optional)—

Modbus digital communication.

CALIBRAtIon—

All units are factory set and calibrated to carbon dioxide.

Routine calibration of the Eclipse CO

2

detector after

completion of initial commissioning is supported, but

not absolutely required. Generally, an annual gas bump

test or full calibration will ensure proper sensitivity and

response.

NoTe

Frequent visual inspections of the detector are
recommended to confirm that there are no external
impediments to proper detection capability.

Four methods of initiating Calibration are supported:

On-Board magnetic reed switch

HART communication

Remote calibration line for remote switch

MODBUS communication

RESPonSE tIME (Det-tronics verified)—

T50 = 6 seconds.

vIBRAtIon—

PIRECL successfully passes Sinusoidal Vibration

Testing in accordance with MIL-STD-810C, Method

514.2, Paragraph 4.5.1.3, Figure 514.2-7 Curve AW, and

C22.2 No. 152-M1984, and also DET NORSKE VERITAS

Certification Notes – No. 2.4 dated May 1995.

ACCuRACy (Det-tronics verified)—
0-20000 ppm or 0-2%/vol:

±10% Full Scale @ 25°C.

SELf-DIAGnoStIC tESt—

Fail-Safe operation ensured by performing all critical

tests once per second.

InGRESS PRotECtIon—

IP66/IP67 (DEMKO Verified).

DEtECtoR HouSInG MAtERIAL—

316 stainless steel (CF8M).

SuRfACE PREPARAtIon—

Electropolish.

ConDuIt EntRy oPtIonS—

Two entries, 3/4 inch NPT or M25.

HARt CoMMunICAtIon PoRt (optional)—

Intrinsically Safe (I.S.). For live maintenance, follow

Control Drawing 011975-001 in Appendix H.

oPtICS PRotECtIon—

The three-layer weather baffle assembly is UV-resistant,

static-dissipating black Polythalimide plastic. The

standard weather baffle version, recommended for most

outdoor and indoor applications, includes an internal

hydrophobic filter. The standard weather baffle includes

a 3/16” (4.8mm) barb fitting for attaching a 3/16” I.D.

hose during calibration.
Heated optics minimize condensation to ensure reliable

operation through temperature extremes.

WIRInG tERMInALS—

Field wiring screw terminals are UL/CSA rated for up to

14 AWG wire, and are DIN/VDE rated for 2.5 mm

2

wire.

Screw terminal required torque range is 3.5–4.4 in.-lbs.

(0.4-0.5 N·m).

ELECtRICAL SAfEty CLASSIfICAtIon—

Installation Category (Overvoltage Category) II

& Pollution Degree 2 per ANSI/ISA-S82.02.01,

EN 61010-1 & IEC 61010-1.