beautypg.com

Specifications – Det-Tronics PIRECL Infrared Carbon Dioxide Gas Detector PointWatch Eclipse User Manual

Page 5

background image

3

95-8676

2.1

SpecificAtionS

InPut voLtAGE (All Models)—

24 Vdc nominal. Operating range is 18 to 32 Vdc.

Ripple cannot exceed 0.5 volts Peak-to-Peak.

PoWER ConSuMPtIon (All Models)—
Detector without relays

4.0 watts nominal @ 24 Vdc

7.5 watts peak @ 24 Vdc

10.0 watts peak @ 32 Vdc.

Detector with relays

5.5 watts nominal @ 24 Vdc

8.0 watts peak @ 24 Vdc

10.0 watts peak @ 32 Vdc.

tEMPERAtuRE RAnGE—

Operating: See CSA, ATEX/CE, and IECEx Appendices.

Storage:

–55°C to +85°C (–67°F to +185°F).

HuMIDIty—

0 to 99% relative humidity (Det-Tronics verified).

GAS DEtECtIon RAnGE—

0-2%/vol factory default

DEtECtABLE GAS—

Carbon Dioxide (CO

2

)

DEtECtoR ConfIGuRAtIon oPtIonS—

A significant number of PIRECL configuration parameters

are field programmable including measurement

range, alarm setpoints, tag number, special notations,

password protection, etc. Details are provided in the

HART Communication Appendix. Two PIRECL field

configuration programming methods are supported:

HART Communication

RS-485 MODBUS Communication

tHIRD PARty ADDRESSABLE MoDuLE (optional)—

Input Voltage: 30 Vdc.

Input Current: 30 mA.

WARM-uP tIME (All Models)—

Device enters normal mode after two minutes upon cold

power-up. One hour warm-up time is recommended

for optimum performance. Signal output level during

warm-up is programmable.

CuRREnt outPut—

Linear 4-20 mA (current source/sink, isolated/non-

isolated) rated at 600 ohms maximum loop resistance @

24 Vdc operating voltage.

vISuAL StAtuS InDICAtoR (All Models)—

Tri-color LED:

Red =

Low alarm, high alarm, or calibration.

See Table 1 for Details.

Green =

Power on / OK

Yellow =

Fault or warm-up.

RELAy outPutS (optional)—

Available on Ex d approved models only.

ALARM RELAyS—

Low and High

Form C Type (NO/NC).

De-Energized during Normal mode, Energized on Alarm.

Contact Rating: 5 amperes at 30 Vdc.

Programmable for Latching or Non-Latching Operation.

Setpoint Range (both): 10-60% of range.

Factory Default Settings:

Low:

40% of range – Non-latching

High: 60% of range – Non-latching

Alarm relay programming can be accomplished using

HART or MODBUS.

CaUtIon

The PIReCL Co

2

Gas Detector should be used in

conjunction with an appropriate certified Control
Unit and configured for a non-latching high alarm.
The control unit must

always latch and require a

deliberate manual action to clear a high gas alarm.
When used as a stand alone device, the high alarm
must always be programmed for latching operation.