APG IRU-9400 user manual User Manual
Page 28
![background image](/manuals/554676/28/background.png)
IRU Series
Rev. B1 3/10
28
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Type 5 or “Hysteresis Far” activates the output whenever the target moves
beyond the trip distance + trip window. Once active, the output will remain
active until the target moves closer than the trip distance, at which point the
output deactivates. Once deactivated, the output will remain deactivated until
the target once again moves beyond the trip distance + trip window.
TYPE 0
NEAR
TYPE 1
EXCLUSIVE
TYPE 3
FAR
TYPE 4
INCLUSIVE
TYPE 2
HYSTERESIS
NEAR
TYPE 5
HYSTERESIS
FAR
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
TRIP
WINDOW
TRIP
DISTANCE