IRU Series
Rev. B1 3/10
10
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
• Hazardous Location Installation
The models listed below are CSA C/US certified for use in Class I, Division 2,
Groups C and D, T6; Ex nA IIB T6, IP65; Class I, Zone 2; AEx nA IBB, T6,
IP65 hazardous locations
:
IRU-2125, IRU-2423, IRU-2425, IRU-3135, IRU-3433, IRU-3435, IRU-
5413, IRU-5415, IRU-5423, and IRU-5425
Parameters for hazardous location installations:
1. Ambient temperature between -30
0
C to 60
0
C (-22
0
F to +140
0
F).
2. Humidity up to 100%
3. Pollution degree 2
4. Installation category II
5. Altitude up to 2000 meters
6. Indoor and/or outdoor use
7. 24 Vdc supply voltage
8. Supply voltage fluctuations must not exceed 10% of nominal supply voltage.