beautypg.com

Aerovent IM-201 User Manual

Page 5

background image

Aerovent IM-201

5

4. Install push rod and tighten ball joint.

5. Adjust limit switches per Section 3.2.1.3.
3.2.1.5 Actuator Pitch Adjustment

The maximum and minimum blade pitch is mechanically

set in the rotor. The limit switches in the actuator can be reset

to reduce the range between these limits to provide different

maximum and minimum airflows. This may be done as follows:

1. Remove terminal box and/or end covers from actuator as

required.

2. Energize terminals, according to the owner's manual, with

120 VAC to drive the blades to minimum pitch.

3. Start the fan and energize the proper terminals, accord-

ing to the owner's manual, to increase the pitch until the

desired maximum airflow is obtained.

4. Adjust limit switch (LS1), according to the owner's man-

ual, to open at this position. This will stop the motor at

the new maximum pitch position.

5. Energize terminals, according to the owner's manual, to

decrease the pitch until the desired minimum airflow is

obtained.

6. Adjust limit switch (LS2), according to the owner's man-

ual, to open at this position. The motor will stop at the

new minimum pitch position.

7. Check limit switch adjustment by driving motor through

range.

8. Replace terminal box and/or end covers as required.
3.2.2 FPMC Fan, Handwheel Version

An external handwheel on the vane section is con-

nected to a miniature wormgear jack inside the core of the

vane section. This in turn is connected to the hub cover of

the rotor. If the handwheel is installed on the right side of

the fan, looking in the direction of airflow, counterclockwise

rotation of the wheel will increase blade pitch. If installed on

the left side, clockwise rotation will increase pitch. With this

arrangement the blade pitch can be changed while the fan is

running.
3.2.3 FPMC Fan, Quadrant

With this version of the FPMC, the external linkage to

the rotor is clamped in one position by a handwheel on a fixed

bolt. The blade forces are such that the fan must be turned off

to adjust the blade pitch. Move the lever upstream to decrease

pitch, downstream to increase it.
3.3 AXICO FPDA FAN

The FPDA fan is an adjustable pitch fan. The blade

pitch has been factory set to meet the airflow requirement of

the job specification. The blade pitch may be changed to meet

other airflow requirements. The hub fairing is marked with

degree marks at the leading edge of the fan blade The first

mark near the inlet side of the fairing is 60°. The last mark

near the center of the fairing is 25°. The intermediate marks

are in 5° increments. The marks are referenced to the center

of the leading edge of the fan blade.
3.3.1 Blade Pitch Adjustment

To set the blade pitch proceed as follows:

NOTE: An 8 mm key with a square drive adaptor fitted

to a torque wrench is required.
1. Remove the stator section access panel per steps 1 through

5 of Section 5.7 to gain access to the fan blades on

Arrangement 4 Type 2 fans. Access on other fans may be

gained by removal of the protective inlet screen if desired.

2. Loosen the four M12 blade bolts until the blade is free to

rotate.

3. Rotate the blade to align the center of the leading edge with

the desired pitch mark.

CAUTION: Do not exceed 55° blade pitch without consult-

ing factory.
4. Alternately tighten opposite blade bolts to 40 ft-lb.
CAUTION: It is important that the bolts are torqued to the

specified value. Do not hand-tighten the bolts.
5. Repeat Steps 2 through 4 for all blades.

6. Replace stator section access panel or inlet screen.
CAUTION: The motor current should be checked not to

exceed the nameplate rating when blade pitch has been

increased.

4.0 INSTRUMENTATION (PITCH

CONTROL) AXICO FANS

4.1 GENERAL

Various parameters such as pressure, temperature, gas

concentration, relative humidity, or velocity can be measured

to provide the required system airflow. The sensor is connect-

ed to a controller which provides an electrical or pneumatic

control signal to the fan. The fan pitch is modulated to meet

the system airflow set point requirement.
4.2 FPAC FAN

The FPAC AXICO fan is factory adjusted to go from

minimum to maximum pitch with a 3 to 15 psig pneumatic

control signal. Two-position or multi-position pitch settings

may be obtained with intermediate control pressures. The

blade pitch may also be manually controlled by supplying the

control pressure from a pressure regulator.
4.3 FPMC FAN

The FPMC fan actuator is adjusted at the factory to go

from minimum and maximum pitch with limit switches at the

ends of the stroke. The limit switch settings may be changed

to reduce the range of blade pitch for two-position step

control from contact closure. See Figure 3 for typical wiring

diagram.
4.4 PARALLEL FAN OPERATION

When two or more fans are installed to operate in par-

allel, two problems are commonly experienced.

1. When less than all the fans are in operation, air circulates

backwards through the fan that is shut down, causing it to

freewheel backwards. This can be very damaging to the

motor when the fan is restarted.

2. When all fans are running together, they may not be com-

pletely stable.

SOLUTION: The signal to all fans must be a common

signal, and it should be a heavily damped signal so the changes

of blade angle occur very slowly. Also the fans must have their

positioners calibrated so that all positioner arms are at the

same angle for a given control pressure. A second check can

be made to insure that motor amps match within 5% at a given

signal pressure.

NOTE: STARTING A FAN WHILE THE ROTOR

ASSEMBLY IS WINDMILLING BACKWARDS VOIDS

ALL MOTOR AND FAN WARRANTIES.