beautypg.com

Notice – Burnham V9A User Manual

Page 39

background image

39

M.

BOILER PIPING, DOMESTIC HOT WATER

(DHW) APPLICATION – The V9A boiler can be

used in many different piping applications to produce

Domestic Hot Water (DHW). In some applications,

depending on the control strategy (outdoor reset,

setpoint operation, etc.) and size of boiler, it is

recommended to isolate the space heating load from

the DHW load. For example, if the domestic load is

more than the space heating load, it is beneficial to

dedicate one or more boilers solely to DHW production

and one or more other boilers to solely space heating,

since during mild weather conditions, the boiler(s)

will have more capacity than is required. Piped in the

recommended manner, the space heating boiler(s) can

be shut down during the summer months to conserve

energy and to avoid short cycling. This section

will address four methods of piping and controlling

domestic hot water generation.
1. Hot Water Boiler/Tankless Coil(s) - Tankless

coils, mounted into the side of the boiler, have

been used successfully for many years and may

be used in single and multiple boiler applications.

When a boiler is arranged with tankless coils, it

is not recommended that outdoor reset be used,

unless there are control systems in place to prevent

overheating of the space heating zones.

Figure 37a depicts the addition of an automatic

mixing valve to the tankless heater piping to obtain

a dual temperature domestic system. The mixing

valve provides tempered water to the fixtures,

while the branch prior to the valve provides high

temperature water for dishwashing, washing

machines and other appliances.

2. Hot Water Boiler/Tankless Coils/Storage Tank - This

application involves the use of several tankless coils

piped in parallel, emptying into a large storage tank,

and is typically used in larger DHW production

applications, such as hotel showers and laundries.

See Figure 37b for recommended piping and wiring

details for this type of application. The tempering

valve and recirculation loop are advantageous in

these applications, because they provide both high

temperature and tempered domestic hot water to

the system, eliminating the need to purge and waste

water until it reaches the desired temperature. In

the case where the boiler is used for domestic

production only, and there is no space heating

involved, a destratification pump is utilized to

provide flow within the boiler. This flow acts as a

means of preventing the hot water from stratifying

at the top of the boiler. Destratification pump flow

rates are given in the table in Figure 37b.

3. Hot Water Boiler/Indirect Water Heater - The use

of indirect water heaters for domestic hot water

generation is common and somewhat advantageous

over tankless coils alone, since they also provide

DHW storage. A tempering valve and recirculating

pump are again recommended for a dual temperature

system, to provide a constant temperature to the

fixtures without waiting for cooler water to warm

up. Figure 37c shows a typical indirect heater

piping application with no space heating. Indirect

pump flow rates are calculated based on a 20°F DT.

NOTICE

DO NOT use the boiler circulator as an indirect

domestic hot water system circulator.

4. Steam Boiler/Indirect Water Heater – Use the

Indirect Water Supply tapping, “R” (Special Order

Only – see Figure 24) when connecting an Indirect

Water Heater directly to the boiler.

NOTICE

When possible, domestic hot water production should utilize a dedicated boiler(s). This will allow the other

boiler(s) to be shut down and isolated during the summer months. If the boiler load is shared between

heating and domestic hot water, then one needs to determine if a hot water priority is required. If a priority

is not selected, erratic domestic hot water production may result during the beginning and end of every

heating season. Conversely, a priority for domestic hot water production may cause a significant heating

zone activation delay, in an improperly balanced system. Parallel piping conversions may require isolation

from the heating system to prevent system flow influence on DHW performance. Consult a qualified system

heating professional to design for the proper application.