beautypg.com

Burnham V9A User Manual

Page 20

background image

20

SECTION III - INSTALLATION INSTRUCTIONS

A.

INSTALL CANOPY/FLUE OUTLET ASSEMBLY,

Refer to Figures 14, 15 and 16.
1. Open canopy carton.
2. Attach the two (2) canopy brackets to the front end

cap of canopy with four (4) #10 x 1/2” sheet metal

screws each.

3. Across the top of the front section and along the top

ledges running back each side of the sections, place

continuous 2” wide strips of cerafelt and overlap

joints at front corners. Cerafelt strip should extend

1/4” beyond rear surface of back section. Cut off

excess.

4. Place the canopy on the sections.
5. Position rear flange (end with studs) of canopy flush

with rear surface of back section.

6. Loosely attach the canopy brackets to the lugs on

the front section of the block assembly with 5/16”

carriage bolts, flat washers and locknuts.

7. Check to see if rear flange of canopy is still flush

with raised flange on back section.

8. Open either the rear flue outlet carton (standard) or

top flue outlet carton (optional).

9. Attach the 1/8” x 1” wide self-adhesive fiber gasket

to the surface of either the rear flue outlet damper

assembly or rear flue outlet cover that mounts

against the canopy and back section. Gasket must

be centered over all attachment holes. Do not

overlap corners, cut butt joints.

10. Attach either the rear flue outlet damper assembly

or rear outlet canopy cover to the canopy with the

5/16” flat wasters, lock-washers and brass

nuts and tighten securely. Attach the rear flue

outlet damper assembly or cover to the back section

with the four (4) 5/16” flat washers and cap screws

and tighten securely.

11. Tighten front canopy carriage bolt until canopy is

secure.

12. On the longer canopy sizes, Intermediate Mounting

Brackets are provided, two (2) are required on sizes

V907A thru V909A and four (4) are required on

sizes V910A thru V912A. Refer to Figures 17 and

18.
a. Intermediate brackets are shipped flat. Bend

side flanges down approximately 90° as shown.

Adjust bends until holes in bracket match hole

pattern on canopy.

b. Secure brackets to both sides of canopy with

three (3) #10 x ½” sheet metal screws per

bracket.

c. Secure canopy left side bracket(s) with

appropriate canopy ‘J’ bolt(s). Insert threaded

end through holes in brackets and hook ‘J’ bolt

Figure 14: Canopy with Rear Flue Outlet Damper

Assembly (Shown on optional steel shipping skid)

Figure 15: Canopy with Top Flue Outlet Damper

Assembly (Rear Cover Removed)

(Shown on optional steel shipping skid)