beautypg.com

Notice, Warning – Burnham V9A User Manual

Page 10

background image

10

SECTION I - GENERAL INFORMATION (Continued)

A.

INSPECT SHIPMENT carefully for any signs of

damage.
1. ALL EQUIPMENT is carefully manufactured,

inspected and packed. Our responsibility ceases

upon delivery of crated boiler to the carrier in good

condition.

2. ANY CLAIMS for damage or shortage in shipment

must be filed immediately against the carrier by the

consignee. No claims for variances from, or short-

age in orders, will be allowed by the manufacturer

unless presented within sixty (60) days after the

receipt of goods.

B.

LOCATE THE UNIT

1. RECOMMENDED SERVICE CLEARANCE

- Locate the unit in the boiler room so as to

provide ease of venting and adequate clearance

for maintenance, serviceability, and installation of

piping. Refer to Figure 1 for boiler dimensional

data.

FRONT — Provide 43” service clearance for

removal, maintenance, and servicing of burner and

controls.

REAR — Provide a minimum clearance from the

boiler jacket for access to flame observation port,

rear flue damper and vent piping, relief valve, and

boiler return piping. See Table III.

LEFT SIDE — Provide a minimum clearance from

the boiler jacket of 26” for cleaning of flueways and

installation and removal of tankless heater(s).

RIGHT SIDE — Provide a minimum clearance from

the boiler jacket of 12”.

TOP — Provide a minimum clearance from the

boiler jacket of 24”

NOTICE

Recommended clearance for service may be

reduced to minimum clearance to combustible

material. However, increased service and

maintenance difficulty will result.

WARNING

Boiler is suitable for installation on combustible

floor. Do not install boiler on carpeting.
Floor construction should have adequate load

bearing characteristics to bear the weight of

the boiler filled with water (see Table 1). A

boiler foundation similar to the one shown in

Figure 2 is recommended if the boiler room

floor is weak or uneven or if a water condi-

tion exists.

2. FOR MINIMUM CLEARANCES to combustible

materials, See Table II.

3. PROVIDE ADEQUATE FOUNDATION for the

unit. Refer to Figure 2.

Table II: Minimum Clearances To Combustible

Materials (Inches)

Boilers with Top Flue Outlet

Boilers with Rear Flue Outlet

* See Table III for Recommended Service Clearance to

access rear of boiler
NOTES:

1. Listed clearances comply with American

National Standard ANSI/NFPA 31, Installation of

Oil Burning Equipment.

2. V9A Series boilers can be installed in rooms with

clearances from combustible material as listed

above. Listed clearances cannot be reduced for

alcove or closet installations.

3. For reduced clearances to combustible material,

protection must be provided as described in the

above ANSI/NFPA 31 Standard.

A

B

C

D

E

Above

Front

Rear

Sides

Vent Connector

6

24

6

6

18

Flue

Outlet

Size

Top

Flue

Outlet

Rear Flue Outlet

Combustible

Surfaces

Non-Combustible

Surfaces

7” Dia.

18”

37”

22”

8” Dia.

38”

23”

10” Dia.

40”

25”

12” Dia.

43”

28”

Table III: Recommended Rear Service Clearance