beautypg.com

Ds7420i dual phoneline/bell supervision module, Ds7420i dual phoneline/ bell supervision module – Bosch 8-Dec User Manual

Page 97

background image

Accessories for Control Panels and Keypads | Interface Modules | 89

DS7420i Dual Phoneline/

Bell Supervision Module

Features

One Class A input zone
Two supervised 12 VDC signaling outputs

The DS7420i is an accessory board designed for use with
the DS7400Xi control panel. It allows the control to be used
in NFPA 72 installations. The DS7420i provides two
supervised 12 VDC signaling outputs, one Class A (Style D)
input zone, and dual phone line transmission and
supervision.

Functions

One Class A Input zone
The Initiating Device Circuit (Terminals 13-16) is a
Class A (Style D) loop intended for connection of normally-
open (N/O) dry contact initiating devices such as waterflow
switches.

Note

The Class A loop will not support loop powered
devices such as two-wire smoke detectors.

Two Supervised 12 VDC Signaling Outputs
There are two supervised outputs:

Auxiliary Output Circuit: A 12 VDC, special application

supervised output that latches on alarm and resets

upon system reset. It is intended for strobes/indicating

appliances and supplies up to 1.0 A.

Indicating Appliance Circuit (Bell Output): A 12 VDC,

special application supervised output that supplies up

to 1.75 A for vibrating bells.

Certifications and Approvals

Region

Certification

Europe

CE

89/336/EEC, EN55022: 1994 +A1: 1995
+A2: 1997 Class A, EN50130-4: 1995
+A1: 1998 +A2: 2003, EN60950-1:
2001, EN61000-3-2: 2000,
EN61000-3-3: 1995 +A1: 2001
1999/5/EC, EN60950 Dec 1992 (2nd
edition) +A1: 1992 +A2: 1993,
EN50081-1: 1992, EN50082-1: 1992

USA

UL

AMCX: Central Station Alarm Units
(UL1610, UL1635), AOTX: Local Alarm
Units (UL464, UL609), APAW: Police
Station Alarm Units (UL365, UL464),
UTOU: Control Units and Accessories -
Household System Type (UL985)

NYC-MEA

274-93-E, Vol. IV

USA

FCC

Rules, Part 15 - Class B digital device and

Part 68

Canada

IC

Canadian Interference‑Causing Equip-

ment Regulations - Class A digital appara-

tus

Installation/Configuration Notes

Commercial Fire Applications
For Commercial Fire applications, the TR1850 transformer
must be enclosed in the AE-TR16 Transformer Enclosure.
The wiring from the AE-TR16 to the control and the wiring
to the outlet box in conduit must also be enclosed in the AE-
TR16 Enclosure.
Wiring
The DS7400Xi control panel must be installed in
accordance with NFPA 72 guidelines. The system is power
limited except for battery terminals. All wiring entering the
system enclosure must be power limited.

Technical Specifications

Auxiliary Power Requirements

Current (Alarm):

140 mA

Current (Supervisory):

20 mA

Voltage:

12 VDC nominal

Environmental Considerations

Temperature (Operating):

0°C to +49°C (+32° to +120°F)

Inputs Initiating Device Circuit

Max. Loop Resistance:

150 Ω total

Output (Auxiliary Output Circuit)

Current Supplied:

up to 1.0 A

www.boschsecurity.com

Bosch Security Systems B.V.

2