Be 300 lsn remote operating unit, Be 300 lsn remote oper- ating unit – Bosch 8-Dec User Manual
Page 74
66 | Control Panels, Control Centers, and Keypads | NZ 300
BE 300 LSN remote oper-
ating unit
The BE 300 LSN keypad acts as a remote display/control
panel for the NZ 300 LSN. The BE 300 LSN is integrated into
an LSN loop or LSN stub.
Up to eight BE 300 LSN units can be connected.
The display/control panel consists of: buzzer to signal
alarm, general displays (LEDs) for alarms, faults and
operation. Clear text display with 2 lines each of 16
alphanumerical characters (illuminated in event of
dialogue) to show all current reports and information.
Keyboard operation.
Certifications and Approvals
Region
Certification
Europe
CE
BE 300 LSN
Germany
VdS
G 100070, C NZ 300 LSN
Technical Specifications
Operating voltage
•
LSN part
+15 V to +31 V
•
Control center
+9.6 V to +30 V
Current consumption
•
LSN part
2.9 mA
•
Control center
20 mA standby/50 mA with illumi-
nation
Tamper surveillance
Tamper contact
Environmental conditions
•
Operating temperature
-5 °C to +45 °C
•
Storage temperature
-20 °C to +60 °C
•
Housing protection category
IP 40
Housing
•
Material
ABS
•
Color
RAL 9010
Dimensions (H x W x D)
112 x 162 x 29 mm
Weight
0.25 kg
Ordering Information
BE 300 LSN remote operating unit
For displaying and executing operating states
and functions of the NZ 300 LSN
4998031457
Bosch Security Systems B.V.
www.boschsecurity.com
1