MS-LZS Flush-Mount
Magnetic Contact
Features
▶ Conventional flush-mount magnetic contact
▶ VdS class C
▶ Tamper switch
▶ Head-on or parallel flush mounting
▶ Conventional perimeter protection
icConventional magnet contacts are used for opening
surveillance of windows and doors.
Certifications and Approvals
Region
Certification
Europe
CE
MS-LZS
Germany
VdS
G 191100, C MS/MSA-LZS
Installation/Configuration Notes
Installation notes
•
Installation can be parallel or head-on.
•
Head-on flush mounting in ferromagnetic materials is
possible with the EG2 flush-mount housing.
•
The magnet should be fixed in the bore.
1
Contact
2
Magnet
Parts Included
Type
Quant. Component
MS-LZS
1
Recessed mount magnetic contact incl. 6 m
cable
Technical Specifications
Type of installation
Flush, parallel or head-on
Contact
Normally open contact/toggle switch
Permissible contact load
≤ 3 Watt
Switching current
10 A to 100 mA
Switching voltage max.
≤ 30 V_
Switch tolerance
≥ 10
7
Magnet
AlNiCo 500
Switch dimensions
Ø 8 mm x 30 mm
Magnet dimensions
Ø 8 mm x 20 mm
Axial installation distance
5 to 12 mm
Temperature range
-25 °C to 70 °C
Connection cable
6 m, LiYY 4 x 0.14 mm
Protection category
IP68