Pfannenberg DTI 6x01 User Manual
Page 15
GB
085 408 121a
15/60
10.4 Unit characteristics
Modus Time curve
Characteristics
Start-up
mode
t = 0s - < 30s
t = 30s
t = 32s
No function
Internal fan start up
External fan and compressor start up
Flashing sequence of the status indica-
tor: "off-dark-light-dark-off".
Fault signal contact is closed.
Test
mode
t >34s – 64s. Compressor and fans remains in opera-
tion during the period. Flashing se-
quence of the status indicator:
"off-dark-light-dark-off".
Fault signal contact is open.
Should a fault arise during the test mode,
the unit goes into the fault mode and the
status indicator lights up according to the
fault state
(see chapter on Fault diagnosis)
The start-up mode is always additionally activated when the door
limit switch is closed (see Sections 10.5)
10.5 Door contact
To avoid an increased production of condensate and for safety
reasons a door limit switch should be connected to the terminals
provided (see circuit diagram in the interior panel behind the internal
fan or in the accompanying supplement sheet)
By the opening of the switch cabinet door and thus the opening of
the switch all of the motors of the cooling unit are immediately
switched off. After closing of the door the start-up mode (see Sec-
tions 10.4) is run through which ensures a restart-up of the cooling
unit with a time lag.
10.6 Centralised fault indication
The signalling of a fault in the cooling unit is effected by the breaking
of a potential-free contact (see Sections 13). In this way a cable
breakage in the fault signalling line is also signalled.
10.7 Energy mode
(Optional, only for units with Multi-Controller)
1) If the cooling unit is not in active cooling operation for 15 min-
utes, it switches to energy mode. This is shown in "Application
error" rhythm (Consequence 1) by a flashing LED and with "En"
in the display.
2) Energy mode is interrupted by a cooling command (switch
cabinet interior temperature above the target temperature, which
means the cooling unit is in active cooling mode). Cooling mode
is maintained until the target temperature (less hysteresis) is
reached. After an additional 15 minutes the device switches
back to energy mode.
3) If device errors arise in energy mode, the cooling unit will be-
have in accordance with the fault diagnosis.
4) If the target temperature (less hysteresis) is undercut at the
external temperature sensor during energy mode, the internal
fan is switched off. If the target temperature (plus hysteresis) is
exceeded at the external temperature sensor, the internal fan is
switched on.
5) As long as no error occurs in the unit, the fault message output
of the device is closed in energy mode (no error).
10.8 Multimaster – bus
(Optional, only for units with Multi-Controller)
In the multimaster configuration, cooling operation is initiated by the
cooling unit which reaches the operating threshold (Tsetp. + 2K)
first. All of the cooling units connected to the multi-master bus switch
to cooling operation. The cooling mode is terminated by the unit
which is the last to go below the operating threshold (Tsetp. - 2K).
For all cooling units which are operated in combination through a
Multi-Master control, the execution of the energy function is
switched off by the cooling command of one of the units from the
combination.
After the last cooling command, the cooling units return to energy
mode after the lapse of the set delay time
10.9 Setting possibilities
By means of a DIP switch (standard controller) or using the USB-
interface (Multi-Controller), various switch cabinet temperatures as
well as limit temperatures can be selected.
The location of the DIP switch on the control board is shown in the
circuit diagram.
The coding options are represented on the circuit diagram (Stan-
dard-Controller). The circuit diagram is adhered to the interior panel
behind the internal fan and shown in the accompanying supplement
sheet.
Starting with a particular set-temperature in the switch cabinet, an
upper limit temperature can be selected which, if exceeded, will
generate an alarm. On units with Multi-Controller, the lower tem-
perature limit can also be monitored. See accompanying supple-
ment sheet for factory settings.
Hint:
The ECoolPLANT service kit (article no.: 18310000002) can be
used in combination with a PC for optimal maintenance, diagnosis
and unit status monitoring of cooling units with multi-controllers.
The ECoolPLANT service kit is a Pfannenberg software package
that, with the aid of the provided USB-cable (type A/B), allows the
following information to be visualised:
- unit data/status
- parameter settings
- temperature recording
- error memory information
Please find more detailed information about the ECoolPLANT soft-
ware and the possibility to download the software free of charge on
the Internet at www.pfannenberg.com.
CAUTION!
Changes to the parameters of the unit set in the works may
be made only by authorised persons!
Isolate the cooling unit from the mains before changing the
DIP-switch settings. Otherwise the modified settings won't
be accepted.