Connecting the VS-808YC
12
6.3 Controlling via RS-485
You can control a
VS-808YC unit via an RS-485 controller, for example, a
PC (equipped with an RS-485 interface) or a Master Programmable Remote
Control system such as the Kramer
RC-3000.
To connect an
RC-3000 to a VS-808YC unit (see Figure 5):
1. Connect the RS-485 terminal block port on the
RC-3000 to the RS-485
port on the
VS-808YC unit, as follows:
Connect the “ A” (+) PIN on the RS-485 rear panel port of the
RC-3000
to the “ A” (+) PIN on the RS-485 rear panel port of the
VS-808YC unit
Connect the “ B” (-) PIN on the RS-485 rear panel port of the
RC-3000
to the “ B” (-) PIN on the RS-485 rear panel port of the
VS-808YC unit
If shielded twisted pair cable is used, the shield may be connected to
the “ G” (Ground) PIN on one of the units (for example, on the
RC-3000)
2. Set the
VS-808YC unit as MACHINE # 2, according to Table 5 (that is,
DIP 1, DIP 2, and DIP 3 OFF, and DIP 4 ON), and set the other
DIP-switches on the
VS-808YC unit, as follows:
Set DIP 5, DIP 6, and DIP 7 OFF
Set Dip 8 ON (for RS-485 Line Termination with 120 )
KEYBOARD EXTENSION
REMOTE CONTACT
RS-485
RS-232 IN
RS-232 OUT
12 VDC
1 2
1 2 3 4 5 6 7 8 G
4
6
8
10
3
5
7
9
11 12
14
16
O
UT
13
15
IN
RS-485 PINOUT
B
A
_
+
Figure 5: Controlling via RS-485 (for example, using an RC-3000)