beautypg.com

Programs of ramp and soak, Link of programs, Event – NOVUS Controller N1100 User Manual

Page 9: Determination of pid parameters, Maintenance, Problems with the controller

background image

N1100 Controller

NOVUS AUTOMATION

9/11

The master password is made up by the last three digits of the serial

number of the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the

master password is 9 3 2 1.

PROGRAMS OF RAMP AND SOAK

This feature allows the creation of Ramp and Soak Setpoint Profiles

(Programs). Up to 7 different profiles with 7 segments each can be

programmed. Longer profiles of up to 49 segments can be created by

linking 2 or more profiles together.
The figure below displays a profile model:

Figure 8 - Example of a Ramp and Soak program

Once a profile is defined and selected for execution, the controller

starts to generate the SP profile automatically in accordance with the

elaborated program.
To execute a profile with fewer segments just program 0 (zero) for

the time intervals that follow the last segment to be executed.

SV

Time

T1

T2

T3

SP0

SP1

SP2

SP3

T4=0

Figure 9 - Program example with few segments

The program tolerance “ptol” defines the maximum deviation

between PV and SP for the execution of the profile. If this deviation is

exceeded, the program will be halted until the deviation falls to within

the tolerance band.
Programming 0 (zero) in the “Ptol” parameter disables the program

tolerance and the profile execution will continue regardless of the PV

value (time priority as opposed to SP priority).

LINK OF PROGRAMS
It is possible to create a more complex program (up to 49 segments),

joining two or more programs. This way, at the end of a program

execution the controller immediately starts to run the next one, as

indicated in the parameter “LP".
To force the controller to run a given program or many programs

continuously, it is only necessary to link a program to itself or the last

program to the first.

SV

time

T1

T2

T3

T4

T5

T1

T2

T3

T4

SP0

SP1

SP2

SP3

SP4

SP5 / SP0

SP1 SP2

SP3

SP4

Program 1

Program 2

Figure 10 – Example of interlinked programs

EVENT
The Event Alarm function associates the alarms to specific segments

of a program. The information of which alarms are to be activated or

deactivated is given in parameters “ PE1“ to “ PE7. Press the and

keys until the desired alarm numbers are displayed.

The Event Alarm requires that the Alarm function be configured as

“rS “.
Notes:

1. If PtoL is different than zero, the controller will wait for the PV to

reach the first program set point SP0 in order to start the

program execution. Otherwise, it will start promptly.

2. Should any power failure occur, the controller resumes the

program execution at the beginning of the segment where it was

interrupted.

DETERMINATION OF PID PARAMETERS

During the automatic tuning the process is controlled in ON / OFF

mode in the programmed SP. Depending on the process behavior,

oscillations may occur above or below the Setpoint. The automatic

tuning may take many minutes to the concluded, particularly in slow

processes.
When the parameter ATUN is altered to YES, the automatic tuning

is immediately initiated by the controller (provided RUN=YES,

otherwise it will wait until this condition becomes true).
Some recommendations for the automatic tuning process are:

avto

= YES: make sure the controller is set for automatic control

mode.

Disable Ramp & Soak programs configuring Pr n = 0. (the

automatic tuning algorithm expects a stable Setpoint value)

Select a Setpoint that is close or equal to the desired process

Setpoint.

Enable the automatic tuning (atvn = YES).

Enable outputs if not yet enabled (rvn = YES).

The “TUNE” indicator on the display stays lit until the completion of

the automatic tuning process.
For control output types relay or pulse, the automatic tuning

calculates the longest suitable period (cycle time (t) for the PWM

output. The cycle time period may be reduced if the process

experiences some oscillation. When driving a SSR, it’s

recommended to set (t = 1 s.
If the automatic tuning does not result in a satisfactory control, refer

to Table 7 for guidelines on how to correct the behavior of the

process.

PARAMETER

VERIFIED PROBLEM

SOLUTION

Proportional Band

Slow answer

Decrease

Great oscillation

Increase

Rate of Integration

Slow answer

Increase

Great oscillation

Decrease

Derivative Time

Slow answer or instability

Decrease

Great oscillation

Increase

Table 7 - Guidance for manual adjustment of the PID parameters

MAINTENANCE

PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most

common errors found during the controller operation. A final revision

may avoid loss of time and damages.
The controller displays some messages to help the user identify

problems.

MENSSAGE

DESCRIPTION OF THE PROBLEM

----

Open input. No sensor or signal.

Err1

Err6

Connection and/or configuration errors.

Check the wiring and the configuration.

Other error messages may indicate hardware problems requiring

maintenance service. When contacting the manufacturer, inform the

instrument serial number, obtained by pressing the key

for more

than 3 seconds.