N1100 Controller

NOVUS AUTOMATION

6/11

DESCRIPTION OF THE PARAMETERS

PV / SP indication - The upper display shows the

current value of PV. The lower display shows the

control SP value.

avto

Control

Control Mode:

Yes

- Means automatic control mode.

no - Means manual control mode.

Bumpless transfer between automatic and manual.

PV / MV- The upper display shows PV value and the

lower display shows the percentage of the

manipulated variable MV applied to the control

output.
When in manual control, the MV value can be

manually changed by the and keys. When in

auto mode the MV value can only be viewed.
To distinguish the MV display from the SP display,

the MV is shown flashing intermittently.

Pr n

Enable

Program

Execution of Program - Selects the ramp and

soak profile program to be executed.

0 - does not execute program

1 to 7 - number of the program to be

executed

With enabled outputs (RvN = YES), the program

starts right after the program is selected.

rvn

Enables control outputs and alarms.

YES

- Outputs enables.

NO

- Outputs not enabled.

CYCLE OF TUNING

Atvn

Auto-tune

Enables the auto tuning feature for the PID

parameters.

YES

– Auto-tune enable

NO

– Do not execute auto tune.

See the DETERMINATION OF PID PARAMETERS

section for more details.

pb

Proportional

Band

Proportional Band - Value of the term P of the

control mode PID, in percentage of the maximum

span of the input type. Adjust of between 0 and

500.0 %.
Select zero for ON/OFF control.

ir

Integral Rate

Integral Rate - Value of the term I of the PID

algorithm, in repetitions per minute (Reset).

Adjustable between 0 and 24.00.
Displayed only if proportional band≠ 0.

dt

Derivative Time

Derivative Time - Value of the term D of the control

mode PID, in seconds. Adjustable between 0

and250seconds.
Displayed only if proportional band≠ 0.

(t

Cycle Time

Pulse Width Modulation (PWM) period in seconds.

Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band≠ 0.

kyst

Hysteresis

Control hysteresis - This parameter is only shown

for ON / OFF control. Adjustable between 0 and

the measurement input type span.
Displayed only if proportional band = 0.

ACt

Action

Control logic:

re

Control with reverse Action. Appropriate for

heating. Turns control output on when PV is

below SP.

dir

Control with direct Action. Appropriate for

cooling. Turns control output on when PV is

above SP.

bias

Bias function - Allows adding a percentage value

between -100 % and +100 %. to the MV control

output.
The value 0 (zero) disables the function.

ovll

Output Low

Limit

Lower limit for the control output - Minimum

percentage value assumed by the control output

when in automatic mode and in PID.
Typically configured with 0.0 %.

ovkl

Output High

Limit

Upper limit for the control output - Maximum

percentage for the control output when in

automatic mode and in PID.
Typically configured with 100.0 %.

sfst

Softstart

SoftStart Function –

Time in seconds during which

the controller limits the MV value progressively

from 0 to 100 %. It is enabled at power up or when

the control output is activated. If in doubt set zero

(zero value disables the Soft start function).

Sp.a1
Sp.a2
Sp.a3
Sp.a4

Alarm SP: Value that defines the point of activation

for the programmed alarms with the functions “Lo”

or “ki”.
For the alarms configured with Differential type

functions, this parameter defines deviation (band).
Not used for the other alarm functions.

CYCLE OF PROGRAMS

t.bas

Program time

base

Program time base - Defines the time base that will

be used by all Ramp & Soak programs.

Se(

- Time basis in seconds

min - Time basis in minutes

Pr n

Program

number

Selects the ramp and soak profile program to be

edited/viewed. The sequence of parameters that

follows refer to this selected program. Total of 20

programs possible. There are 7 possible programs.

Ptol

Program

Tolerance

Maximum admitted deviation of PV with respect to

SP.If exceeded, the program execution is suspended

(the internal timer freezes) until the deviation be

returns back within the defined tolerance.
The value 0 (zero) disables the function.

Psp0

Psp7

Program SP

Program SP’s, 0 to7: Group of 8 values of SP that

define the Ramp and Soak profile segments.

Pt1

Pt7

Program Time

Segments durations, 1 to7: Defines the time of

duration, in second or minutes, 7 of the segments of

the program being edited.

Pe1

Pe7

Program event

Alarms of Event, 1 to 7: Parameters that define

which alarms are to be activated during the

execution of a certain program segment. The alarms

chosen must have its function configured as “rS”.

Lp

Link Program

Link Program: number of the next profile program to

be linked following the current program. Profiles can

be linked together to produce larger programs of up

to 49 segments

.

0 - do not link to any other program.

1 a 7 – number of the program to be linked to.

PV Indication
(Red Screen)

SP Indication

(Green Screen)

PV Indication
(Red Screen)

MV Indication

(Green Screen)