All registers are 16 bit signed integers.

Address Parameter

Register Description

0000

Active SP Read: Active control SP (main SP, from

ramp and soak or from remote SP).
Write: to main SP.
Range: from spll to spkl.

0001

PV

Read: Process Variable.
Write: Not allowed.
In case of temperature reading, the value

read is always multiplied by 10,

independently of dppo value.

0002

MV

Read: Output Power in Automatic or

Manual mode.
Write: only allowed when in Manual mode.
Range: 0 to 1000 (0.0 to 100.0 %).

SPECIFICATIONS

DIMENSIONS: ........................................ 48 x 48 x 110 mm (1/16 DIN)

............................................................ Approximate Weight: 150 g

CUTOUT IN THE PANEL: ................... 45.5 x 45.5 mm (+0.5 -0.0 mm)
POWER SUPPLY: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz

Optionally: .......................................................... 24 Vac/dc ±10 %

Maximum consumption: ........................................................ 9 VA

ENVIRONMENTAL CONDITIONS:

Operation Temperature: ................................................ 5 to 50 °C

Relative Humidity: ...................................... 80 % max. up to 30 ºC

For temperatures above 30 ºC, reduce 3 % for each ºC
Internal Use; Category of installation II, Degree of pollution 2;

altitude < 2000 m.

INPUT ............. T/C, Pt100, voltage and current (according to Table 1)

Internal Resolution: ................................... 32767 levels (15 bits)

Resolution of Display: ...... 12000 levels (from -1999 up to 9999)

Rate of input reading: .................................. up to 55 per second

Precision: .. Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC

................... Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC

................................................................ Pt100: 0.2 % of the span

............................. 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of the span

Input Impedance: . 0-50 mV, Pt100 and thermocouples: >10 MΩ

................................................................................. 0-5 V: >1 MΩ

................................................ 4-20 mA: 15 Ω (+2 Vdc @ 20 mA)

Measurement of Pt100: .............. Three wires type, (α=0.00385)

with compensation for cable length, excitation current of 0.170 mA.
All input and output types are factory-calibrated. Thermocouples

according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;

ANALOGICAL OUTPUT (I/O5):...... 0-20 mA or 4-20 mA, 550 Ω max.

..... 31000 levels, Isolated, for control or retransmission of PV and SP.
CONTROL OUTPUT:

2 Relays SPST-NA (I/O1 and I/O2): 1.5 A / 240 Vac, general use

.......................... 1 Relay SPDT (I/O3): 3 A / 250 Vac, general use

.......................... Voltage pulse for SSR (I/O5): 10 V max. / 20 mA

............. Voltage pulse for SSR (I/O3 and I/O4): 5 V max. / 20 mA

INPUT OF REMOTE SP: ........................ 0-20 mA, 4-20 mA, 5 V, 10 V

The Remote SP mA inputs require an external resistor of 100 R

connected directly to the terminals 9 and 10 of the controller's back

panel.
ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997

and EN 61326-1/A1:1998
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995
USB INTERFACE 2.0, CDC CLASS (VIRTUAL COMMUNICATIONS

PORT), MODBUS RTU PROTOCOL.
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3

mm;
FRONT PANEL: IP65, POLYCARBONATE - UL94 V-2;
CASE: IP20, ABS+PC UL94 V-0;

PROGRAMMABLE CYCLE OF PWM 0.5, UP TO 100 SECONDS;
STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO

THE POWER SUPPLY;
CERTIFICATIONS
: ..................................... CE / UL (FILE: E300526)

IDENTIFICATION

N1100 -

3R -

485 -

24V

A

B

C

D

A: Controller model:

N1100;

B: Optional I/Os:

Blank: (basic version, without I/O3 nor I/O4);

3R

(SPDT Relay in I/O3);

DIO

(Digital I/Os in I/O3 and I/O4);

C: Digital Communication:

Blank (basic version, without serial communication);

485

(RS485, Modbus protocol)

D: Power Supply:

Blank (basic version, 100 to 240 Vac/dc);

24V

(24 Vac/dc input voltage);

SAFETY INFORMATION

Any control system design should take into account that any part of

the system has the potential to fail. This product is not a protection or

safety device and its alarms are not intended to protect against

product failures. Independent safety devices should be always

provided if personnel or property are at risk.
Product performance and specifications may be affected by its

environment and installation. It’s user’s responsibility to assure

proper grounding, shielding, cable routing and electrical noise

filtering, in accordance with local regulations, EMC standards and

good installation practices.

SUPPORT AND MAINTENANCE

This product contains no serviceable parts inside. Contact our local

distributor in case you need authorized service. For troubleshooting,

visit our FAQ at m

www.novus.com.br

.

LIMITED WARRANTY AND LIMITATION OF LIABILITY

NOVUS warrants to the original purchaser that this product is free

from defects in material and workmanship under normal use and

service within one (1) year from the date of shipment from factory or

from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the

cost of correcting defects in the product or of supplying replacement

product as herein provided and upon the expiration of the warranty

period all such liability shall terminate.
For complete information on warranty and liability limitations, check

appropriate section in our web site:

www.novus.com.br

.