beautypg.com

HID VertX EVO V2000 Installation Guide User Manual

Page 8

background image

VertX EVO V2000 Installation Guide, 72000-902, rev A.2

April 2012

Page 8 of 18

© 2003 - 2012 HID Global Corporation. All rights reserved.

5. Input Connections – Input connections are analog inputs used for a combination of specific functions such as

Request-to-Exit (REX), Door monitor, etc. They can also be used as general purpose monitoring. Connect one side
of the switch or contact to the + (plus) lead and the other to the (minus) lead. The following table shows where the
inputs are located. Pin numbers shown on the cover use the convention +/–.

The default REX input configuration is normally open (NO) unsupervised (no EOL resistors).

However, the default door switch (DS) configuration is Normally Closed (NC), unsupervised (no
EOL resistors). For UL1076 installations, all inputs must be supervised.

All other input points are defaulted for NO switches and are unsupervised (no EOL resistors).

Any input can be configured as NO or NC, as well as unsupervised or supervised. They can be configured
for supervisory resistors of 1K – 6K Ohm. The setup of supervised inputs should be done during
configuration of the VertX EVO devices through the host.

Example: Input 1, V2000 is: P2 Pin1 is + and Pin 2 is -.

Input number

V2000

1

P2 Pins 1/2

Door Monitor

2

P2 Pins 3/4

REX input

3

P5 Pins 4/3

Door Monitor

4

P5 Pins 2/1

Rex Input

5

P7 Pins 8/7

Tamper

6

P7 Pins 6/5

AC Fail

7

P7 Pins 4/3

Batt Fail

Supervised inputs can be configured for:

Except for the door monitor, all other inputs
default to NO, unsupervised: