3. Use Mounting Brackets to attach extrusions to the ceiling or to the tops of cabinets.
• Position the extrusions
so Gusset Joiners
face the outside of the
containment/duct.
• Mounting brackets
attach to the outside of
the containment/duct.
• Support extrusions on
both sides of Joiner
Gussets and close to
the ends of the duct.
• Space brackets
approximately every
48” (1200 mm) of
span.
• Use 3/8” threaded rod
to support the duct
from the ceiling as
shown.
• When cabinets are the
same height, you can
support extrusion(s)
directly from the tops
of cabinets.
• Flip the Mounting
Bracket and use a 3/8”
hex bolt to attach the
extrusion directly to
the tops of cabinets.
• Hardware for ceiling or
cabinet attachment is
not included.