beautypg.com

Horner APG SmartMod HE359RTD100 User Manual

Page 2

background image

MAN0840-04-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

5/11/2009 Page 2 of 2 ECN #

950

3

Init Default Setup

Communication parameters will be set to INIT default after performing the
procedure:

1. Install jumper between INIT and GND terminals of the RS-485 port.
2. Apply power to Smartmod unit.
3. Read parameter words to see current parameters.
4. Write changes if necessary.







The INIT Default RS485 Settings Are:
Modbus ID = 1
Baud rate = 9600
Parity = None
Stop Bits = 1
Data Bits = 8
No handshake




4

Configuration DATA


SmartMod Configuration settings are mapped into Modbus Register space.
This configuration data may be modified with any Modbus/RTU Master device.
For convenience, Horner APG has developed a variety of Cscape application
files which allow an OCS (Xle, NX, LX, QX) to act as a SmartMod configurator.
Initial configuration of SmartMod module should be done on an individual
basis, since all modules come from the factory with a default Modbus ID of 1.
Once each module on the network has its own unique Modbus ID, further
configuration adjustments can be made with the entire network powered.

All configuration parameters listed below (except 40012 Channel Enable) are
stored in EPROM. That means they should not be constantly rewritten.

Configuration Parameters – Registers 40001 through 40013

Modbus

Register

Description

Min

Max

Default

40001-

40005

Reserved

40006

Communications

Parameters

See Table

38.4kbaud,

N, 8, 1, RTU

Mode

40007

Modbus ID

1

255

1

40008

Rx/Tx Delay (in 2mS

steps)

0

255

0mS

40009

Watchdog Timer (in 0.5s

steps)

0

255

10 (5s)

40010

Modbus Coil Data

Not Configuration Data – See

I/O Data

40011

Input Type

See Table

23 (RTD Pt-

100 Type)

40012

Channel Enable

See Table

255 (All

Channels

enabled)

40013

Reserved

Register 40006 (Communications Parameters) Bit Definition

Bits 7-15

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Unused

Mode

Parity

Data

Bits

Baud Rate

Value

Meaning

Value

Meaning

0

Mark

0

1200 baud

0 =

ASCII

Mode

1

Even

0 = 7

Data

Bits

1

2400 baud

2

Odd

2

4800 baud

3

Space

3

9600 baud

1 =

RTU

Mode

1 = 8

Data

Bits

4

19200 baud

5-7

38400 baud

Register 40011 (Input Type) Value Definition

Value

Input Type

7

0-2000ohm Resistance

8

0-500ohm Resistance

23

RTD Pt-100 Type

24

RTD Ni-100 Type

25

RTD Pt-1000 Type

26

RTD Ni-1000 Type


Register 40012 (Channel Enable) Bit Definition

Bit 4-15

Bit 3

Bit 2

Bit 1

Bit 0

Unused

Input 3

Input 2

Input 1

Input 0

0 = Disable Input

1 = Enable Input



5

Input/Output DATA


SmartMod Analog I/O utilizes both Modbus Registers (40001-40030) and Coils (1-11). It is possible
to access all data using Registers only, because the Coils can be accessed through Register 40010.

The following tables lists all Modbus I/O data available.

I/O Register Data (Registers 40014-40022)

Modbus

Register

Description

Access

Minimum

Maximum

Units

40010

Mirror of Coil

Data

Read/Write

n/a

n/a

n/a

40014

Cold Junction

Temperature

Read-only

-1000

6000

0.01 degrees C

40015

Input 0

Read-only

40016

Input 1

Read-only

40017

Input 2

Read-only

40018

Input 3

Read-only

40019

Input 4

Read-only

40020

Input 5

Read-only

40021

Input 6

Read-only

40022

Input 7

Read-only

Depends

on Input

Type

Depends

on Input

Type

0.1C or 0.1 ohm

Modbus

Coil

Description

Access

Watchdog Event & Power-up

Event Operation

00001

Open Detect Input 0

Read/Write

00002

Open Detect Input 1

Read/Write

00003

Open Detect Input 2

Read/Write

00004

Open Detect Input 3

Read/Write

00005

Open Detect Input 4

Read/Write

00006

Open Detect Input 5

Read/Write

00007

Open Detect Input 6

Read/Write

00008

Open Detect Input 7

Read/Write

00009

Watchdog Enabled

Read/Write

00010

Watchdog Event

Read/Write

00011

Power-up Event

Read/Write

If Coil 9 (Watchdog Enabled) is set,

Coil 10 (Watchdog Event) will set if the

Watchdog Timeout value is exceeded.

The Watchdog Timeout value is set in

Register 40009. When set, Coil 10
can be reset by the controller when

normal communications resumes.

The Power-up Event (Coil 11) is set

every time the power is applied. It can

be cleared by the controller if desired.

RTD Sensor Temperature Ranges

RTD Sensor Type

Minimum Temperature

Maximum Temperature

Pt-100

-200 degrees C

+850 degrees C

Ni-100

-80 degrees C

+180 degrees C

Pt-1000

-200 degrees C

+200 degrees C

Ni-1000

-60 degrees C

+150 degrees C

6

Installation / safety



a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields may be terminated at the module terminal strip.
d. In severe applications, shields should be tied directly to the ground block within the panel.
e. Use the following wire type or equivalent: Belden 8441.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:





7

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

INIT

D-

D+

GND

A

B

C

D

Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

Note: There are 2 types of default settings possible:
1. Factory default as described in section 1 (Specifications)
2. Default after INIT as described in section 3 (INIT Default Setup)