beautypg.com

Horner APG SmartMod HE359DAC107 User Manual

Page 2

background image

MAN0838-04-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________

5/11/2009 Page 2 of 2 ECN # 950

3

Init Default Setup

Communication parameters will be set to INIT default after performing the
procedure:

1. Install jumper between INIT and GND terminals of the RS-485 port.
2. Apply power to Smartmod unit.
3. Read parameter words to see current parameters.
4. Write changes if necessary.







The INIT Default RS485 Settings Are:
Modbus ID = 1
Baud rate = 9600
Parity = None
Stop Bits = 1
Data Bits = 8
No handshake







4

Configuration DATA


SmartMod Configuration settings are mapped into Modbus Register space. This
configuration data may be modified with any Modbus/RTU Master device. For
convenience, Horner APG has developed a variety of Cscape application files
which allow an OCS (Xle, NX, LX, QX) to act as a SmartMod configurator. Initial
configuration of SmartMod module should be done on an individual basis, since
all modules come from the factory with a default Modbus ID of 1. Once each
module on the network has its own unique Modbus ID, further configuration
adjustments can be made with the entire network powered.

All configuration parameters listed below (except 40012 Channel Enable) are
stored in EPROM. That means they should not be constantly rewritten.

Configuration Parameters – Registers 40001 through 40013

Modbus

Register

Description

Min

Max

Default

40001-

40005

Reserved

40006

Communications

Parameters

See Table

38.4kbaud, N, 8,

1, RTU Mode

40007

Modbus ID

1

255

1

40008

Rx/Tx Delay (in 2mS

steps)

0

255

0mS

40009

Watchdog Timer (in

0.5s steps)

0

255

10 (5s)

40010

Modbus Coil Data

Not Configuration Data – See I/O Data

40011

Reserved

40012

Reserved

40013

Reserved

40014

Output Type

See Table

0 (All Channels

Current)

Register 40006 (Communications Parameters) Bit Definition

Bits 7-15

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Unused

Mode

Parity

Data Bits

Baud Rate

Value Meaning

Value

Meaning

0

Mark

0

1200 baud

0 = ASCII

Mode

1

Even

0 = 7 Data

Bits

1

2400 baud

2

Odd

2

4800 baud

3

Space

3

9600 baud

1 = RTU

Mode

1 = 8 Data

Bits

4

19200 baud

5-7

38400 baud

Register 40014 (Output Type) Bit Definition

Bit 4-15

Bit 3

Bit 2

Bit 1

Bit 0

Output 3

Output 2

Output 1

Output 0

0 = Current (0-20mA)

Unused

1 = Voltage (0-10V)






5

Input/Output DATA


SmartMod Analog I/O utilizes both Modbus Registers (40001-40030) and Coils (1-11). It is
possible to access all data using Registers only, because the Coils can be accessed through
Register 40010.

The following tables lists all Modbus I/O data available.

I/O Register Data (Registers 40010-40026)

Modbus

Register

Description

Access

Minimum

Maximum

Units

40010

Mirror of

Coil Data

Read/Write

n/a

n/a

n/a

40015

Output 0

Read/Write

0

20000

1uA or 1mV

40016

Output 1

Read/Write

0

20000

1uA or 1mV

40017

Output 2

Read/Write

0

20000

1uA or 1mV

40018

Output 3

Read/Write

0

20000

1uA or 1mV

40019-

40022

Reserved

40023

Default/Safe

Value Out 0

Read/Write

0

20000

1uA or 1mV

40024

Default/Safe

Value Out 1

Read/Write

0

20000

1uA or 1mV

40025

Default/Safe

Value Out 2

Read/Write

0

20000

1uA or 1mV

40026

Default/Safe

Value Out 3

Read/Write

0

20000

1uA or 1mV

Modbus

Coil

Description

Access

Watchdog Event &

Power-up Event

Operation

00009

Watchdog

Enabled

Read/Write

00010

Watchdog Event

Read/Write

00011

Power-up Event

Read/Write

Modbus

Register

Description

Access

40010 bit 0

Watchdog

Enabled

Read/Write

40010 bit 1

Watchdog Event

Read/Write

40010 bit 2

Power-up Event

Read/Write

If Coil 9 (Watchdog
Enabled) is set, Coil 10
(Watchdog Event) will set
if the Watchdog Timeout
value is exceeded. The
Watchdog Timeout value
is set in Register 40009.
When set, Coil 10 can be
reset by the controller
when normal
communications
resumes.

The Power-up Event
(Coil 11) is set every time
the power is applied. It
can be cleared by the
controller if desired.




6

Installation / safety




a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields may be terminated at the module terminal strip.
d. In severe applications, shields should be tied directly to the ground block within the panel.
e. Use the following wire type or equivalent: Belden 8441.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:






7

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

INIT

D-

D+

GND

A

B

C

D

Warning: Remove power from the OCS controller, CAN port, and any peripheral
equipment connected to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

Note: There are 2 types of default settings possible:
1. Factory default as described in section 1 (Specifications)
2. Default after INIT as described in section 3 (INIT Default Setup)

This manual is related to the following products: