beautypg.com

2 wiring – Horner APG SmartStack I/O HE-DIQ722 User Manual

Page 2

background image

PAGE 2

10 NOV 2006

MAN0315-07

DIQ722

Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.

2 WIRING

2.1

Input / Output Connector Wiring

Warning:

To protect the module and associated wiring from load faults, use external (

10 A)

fuse(s) as shown. This warning affects DIQ722, Revisions C or higher.

Warning:

Connecting high voltage to any I/O pin may cause high voltage to appear at other I/O

pins.

Warning:

Wiring the line side of the AC source to loads connected to outputs 1 through 10 and

the neutral side of the AC source to the output common(s) would create a Negative Logic
condition, which may be considered an unsafe practice.

*

OCS Bottom View – Shows

Corresponding I/O Pin

Signal

Pin

DIQ722

I1 Input

1

I2 Input

2

I3 Input

3

I4 Input

4

C1

Common for Inputs

1,2,3,4

Q1 Output

1

Q2 Output

2

Q3 Output

3

Q4 Output

4

Q5

Output 5

C2 Common

for

Outputs

1,2,3,4,5

Q6 Output

6

Q7 Output

7

Q8 Output

8

Q9 Output

9

Q10 Output

10

C3 Common

for

Outputs

6,7,8,9,10

VC

Relay Coil power common,

connected to bus common

internally.

V+

Relay Coil power + 18 to

+30VDC, 90mA max.

*

LOAD

I1

I2

I3

I4

Q3

C2

V+

Q5

C3

VC

Q1

Q2

C1

Q4

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

LOAD

Q9

Q8

Q7

Q6

Q10

C3

Q9

Q10

120VAC

L

N

18-30VDC

001DIQ013-R1

5-250VAC

OR

5-30VDC

N
L

5-250VAC

OR

5-30VDC

N
L