OUTPUT CONVERSION FACTOR

The following table describes how program data values are scaled to real-world analog voltage outputs by
the module. Given a desired output current, the data value is converted by using the conversion factor
from the table. The following formula is used: Data = Output Current (mA) / Conversion Factor

Example:

The user selects a current range of +20 mA:

1) The desired output current is 12 mA.
2) Using the table, the conversion factor for the current range of +20 mA is 0.000625.
3) To determine the data value, the formula is used:

Data = Output Current (mA) / Conversion Factor
19200 = 12 mA / 0.000625

Conversion of Real-World Outputs into Controller

Selected Current

Range

OutputCurrent (mA)

Data

Conversion Factor

+20.47 32752

+20.00 32000

0 to +20 mA

0 0

0.000625

0

200

400

600

800

1000

1200

1400

0

5

10

15

20

25

30

35

Current (mA)

Loo

p

L

o

ad Resi

stance

(π

)

Operating Area