MAN0453-04
DAC106
Information is subject to change without notice. SmartStack is a trademark of Horner APG, LLC.
5
OUTPUT CONVERSION FACTOR
The following table describes how program data values are scaled to real-world analog voltage outputs by
the module. Given a desired output current, the data value is converted by using the conversion factor
from the table. The following formula is used: Data = Output Current (mA) / Conversion Factor
Example:
The user selects a current range of +20 mA:
1) The desired output current is 12 mA.
2) Using the table, the conversion factor for the current range of +20 mA is 0.000625.
3) To determine the data value, the formula is used:
Data = Output Current (mA) / Conversion Factor
19200 = 12 mA / 0.000625
Conversion of Real-World Outputs into Controller
Selected Current
Range
OutputCurrent (mA)
Data
Conversion Factor
+20.47 32752
+20.00 32000
0 to +20 mA
0 0
0.000625
0
200
400
600
800
1000
1200
1400
0
5
10
15
20
25
30
35