beautypg.com

Horner APG Text OCS OCS110 User Manual

Page 4

background image

PAGE 4

26 JUL 2004

MAN0416-04

2.2.3

RS-232 Programming Port and Wiring

Table 4– RS-232 Port Pins

Pin

Signal

Description

Direction

1 DCD

Always

high

Out

2 RXD

Received

Data Out

3 TXD Transmitted

Data In

4

DTR

Data Terminal Ready

In

5 GND

Ground

-

6

DSR

Data Set Ready

Out

7

RTS

Request to Send

In

8

CTS

Clear to Send

Out

9 RI

Ring

Indicate Out






Figure 7 – RS-232 Port

The OCS units feature an RS-232 port (Programming/Debug) for connection to a personal computer.
This port is used for the purposes of OCS programming, configuring, monitoring, and debugging. This
port can also be used for general ladder logic controlled serial communications to printers, modems,
terminals, etc. When ladder has control of this port, it is not available for programming or debugging. The
wiring diagram for the RS-232 port is shown in Figure 8. If a permanent connection is to be made
between the OCS and the personal computer, the use of a shielded, multiple conductor wire with a
maximum length of 15.24 meters (50 feet) enables proper performance.

















Figure 8- OCS to PC Wiring Diagram


Pin 9

Pin 1

OCS RS-232

9-PIN PC COM

SHIELDED MULTI CONDUCTOR

DCD 1

1 DCD

RXD 2

TXD 3

DTR 4

GND 5

DSR 6

RTS 7

CTS 8

RI 9

2 RXD

3 TXD

4 DTR

5 GND

6 DSR

7 RTS

8 CTS

9 RI

DB9

MALE

DB9

FEMALE

15.24 METERS MAX

(50 FEET MAX)

This manual is related to the following products: